Product Features FMQ4G series ATSE is composed of two parts: switch body and
changeover control. The switch is driven by solenoid coil and has
fast changeover speed. Type NA is a special integrated ATSE, with the intelligent
controller installed inside the switch body in a compact structure,
so that the user only needs to connect the main circuit and then it
can be put into use, which is convenient for the user to connect. N, C, M type is split external control, the controller and the
switch body are connected with a special cable to make the
installation and wiring more convenient. The N, C, M type is split
type external control, the controller and the switch body are
connected by a special cable to make the installation and wiring
more convenient. The integral type and split type also have the
function of detecting fault such as overvoltage, undervoltage and
shortage of two-way three-phase power supply, and the function of
starting and stopping signal output of generator set can be added
as an option (about 3 seconds delay when the main power supply
fails, and about 3 seconds delay when the main power supply returns
to normal). Main technical parameters Product category | PC class double power automatic transfer switch | Frame class | Product code | Frame class | NA,N,C | 32A,63A,125A,250A,400A,630A | M | 1600A | Q | 3200A | Product code | Product code | Operating current | Features | | NA | 16A-630A | One-piece two-section type, intelligent type, 250 ~ 630A with IJ
inlet optional | | N | 16A-630A | split two-section type, terminal block wiring, 250 ~ 630A same side
inlet optional optional | C | 16A-630A | split two-section type, air plug wiring, 250 ~ 630A same side inlet
optional | M | 630A-1600A | split two-section type | Number of poles | 2P(125A and below),3P.4P | Rated current | 16A-3200A | Working mode | R (default self-repeat), S (self-repeat/standby), B (ll-way
priority), Note: factory default self-repeat | Optional functions | F (grid - generation), T (communication) |
| FMQ4G-32NA | FMQ4G-63NA | FMQ4G-125NA | Rated operating current (A) | 16,20,25,32 | 40,50,63 | 80,100,125 | Rated control power current (A) | 5 | Rated short-time withstand current (kA) | 10 | Rated impulse withstand voltage (kV) | 8 | Use category | AC-33B | | Mechanical | 20000 | Electrical | 6000 | Number of poles | 2P 3P 4P | 2P 3P 4P | 2P 3P 4P | Weight (kg) | 4.2 4.7 5.2 | 4.2 4.7 5.2 | 5 5.5 6.5 | Operation cycle (sec/time) | 10 |
|