Brand Name SKYLINE
Model Number GJL-2
Certification CE
Place of Origin CHINA
Minimum Order Quantity 1 unit
Price negotiated
Payment Terms T/T, L/C, Western Union, MoneyGram
Supply Ability 1 unit/ month
Delivery Time 10 work days
Packaging Details plywood case
Standards GB 14907-2002 Steel-Structure Fireproof Coating,GB T9978-2008 Fire Resistance Test Method for Building Components, GB T23864-2009 Plugging Material of Fireproof
Operating Voltage AC 380V±10% 50Hz
Air Flow 0-50 m³/min Measurement Accuracy: ≤ +/-0.5 m³/min
Timing Range 0-360 min;Timing Accuracy: < +/-2s
Maximum of Burning Length of the Sample 1600mm
Detailed Product Description
Steel-Structure Fireproof Coating Sample Test Furnace High Accuracy 3KW
 

Technical indicators

 Operating Voltage AC 380V +/-10% 50Hz ; Electric power: 3KW
 Stove  Pressure Measurement Range 0-100Pa Measurement Accuracy: ≤ +/-3Pa
 Air Flow 0-50 m³/min Measurement Accuracy: ≤ +/-0.5 m³/min
 Burning Airflow Propane ,Liquefied gas
 Gas Flow 0-100 L/min;Measurement Accuracy:2.5 level
 Tank Capacity 50 kg*2
 Test Temperature Program warming:60min room temperature-925℃;120min room temperature-1050℃;180min room temperature-1115℃;240min room temperature-1150℃;300min room temperature-1180℃; 360min room temperature-1210℃;
 Equipment Precision a.furnace temperature: +/-15℃;b.internal specimen temperature: +/-10℃; c.backfire specimen temperature: +/-4℃
 Temperature Sensor a.armored platinum rhodium platinum value S thermocouple
accuracy class:II level;b.armored nickel-chromium nickel-silicon value K thermocouple
accuracy class:II level
 Timing Range 0-360 min;Timing Accuracy: < +/-2s
 Maximum of  Burning Length of the Sample 1600mm
 Instrument Dimensions Test plate bracket 670mm*670mm*1100mm;Control box 800mm*500mm*500mm

 

Features
1.PLC+NA view professional software, touch screen control, easy operation
2. The whole process of testing is fully automated
3. Temperature errors are lower than the national standard

 

Design Standards
GB14907-2002 Steel-Structure Fireproof Coating
GB T9978-2008 Fire Resistance Test Method for Building Components
GB T23864-2009 Plugging Material of Fireproof