China Split Case Fire Pump manufacturer
Wuhan Spico Machinery & Electronics Co., Ltd.
Your Reliable Fire Pump Solution Partner for Global Emerging Markets
10
Home > Products > Fire Pump Controller >

NFPA 70 STANDARD TORNATECH Diesel Engine Fire Pump Controller GFD 24-220

Browse Categories

Wuhan Spico Machinery & Electronics Co., Ltd.

City: wuhan

Province/State:hubei

Country/Region:china

Tel:86--18627949609

Contact Person:
Ms.Kathy Wong
View Contact Details

NFPA 70 STANDARD TORNATECH Diesel Engine Fire Pump Controller GFD 24-220

Brand Name Tornatech
Model Number GFD24-220
Certification NFPA 70
Place of Origin Canada
Minimum Order Quantity 1set
Payment Terms L/C, T/T
Delivery Time 45~60 Working Days after receipt of deposit
Packaging Details Export Package
Price Negotiation
Brand Tornatech
Function Control Panel for Fire Pump
Material Cast Iron
Protection Grade IP54
Color Red
Standard NFPA 70
Detailed Product Description

NFPA 70 STANDARD TORNATECH Diesel Engine Fire Pump Controller GFD 24-220

 

DEMANDS INFO FORM Kathy.pdf

 

Diesel engine fire pump controllers are designed to automatically start a diesel engine driven fire pump

upon detection of a pressure drop in the fire protection system. A diesel engine fire pump controller

provides automatic & manual starting and stopping. An automatic start is controlled by a pressure transducer

or by remote automatic devices such as a deluge valve. A manual start is controlled by remote manual button

or by controller pushbutton. The automatic shutdown option provides a 30-minute automatic stop after automatic

start once all starting causes have returned to normal. The diesel engine fire pump controller includes two battery

chargers to ensure the engine batteries are continuously charged.

 

Methods of Starting 

 

AUTOMATIC START
The controller will start automatically on low pressure detection by the pressure sensor when the pressure drops

below the cut-in threshold.
MANUAL START
The engine can be started by pressing the CRANK 1 or and/or CRANK 2 push button, regardless of the system pressure,

when the Main Selector switch is in the HAND position. The Fuel Solenoid Valve will open as soon as a CRANK button is

pressed and will remain in this state.
REMOTE MANUAL START
The engine can be started from a remote location by momentarily closing a contact of a manual push button.
REMOTE AUTOMATIC START, DELUGE VALVE START
The engine can be started from a remote location by momentarily opening a contact connected to an automatic device.

The controller must be in automatic mode.
SEQUENTIAL START
In case of a multiple pump application, it may be necessary to delay the starting of each motor when there is a water pressure

drop to prevent simultaneous starting of all motors.

 

FLOW START, HIGH ZONE START
The pump can be started by opening/closing a contact on the FLOW/ZONE START/STOP input.
WEEKLY START
The engine can be started (and stopped) automatically at the preprogrammed time.
TEST START
The motor can be started manually by pressing the run test button.

 


 


 