China Flammability Test Apparatus manufacturer
Dongguan HOOHA Electrical Equipment Company Limited
Make wire and tube business easy.
8
Home > Products > Smoke Density Tester >

High Precision JB / T 10707 Smoke Emission Test , NES713 Smoke Density Test Apparatus

High Precision JB / T 10707 Smoke Emission Test , NES713 Smoke Density Test Apparatus

Brand Name HOOHA
Certification NES 713/JB/T 10707
Place of Origin China
Minimum Order Quantity 1
Price 3000-80000USD/PC
Payment Terms L/C, T/T, Western Union
Supply Ability 10 sets/per month
Delivery Time 30 working days
Packaging Details wood package
Model YY435
Size 1,185(W)×700(D)×2,100(H) mm
Power AC 220V, 50/60Hz, 10A
Weight About 150kg
Instructions Supplied
Exhaust 50L/s
Detailed Product Description

Description:

 

This tester measures the Toxicity Index by ppm in Naval Engineering Standard chamber when complete combustion occurs by burner.

NES 713 TOXIC Chamber meets the standard of NES 713 and is used to measure combustion characteristics about materials.

NES 713 Toxic Chamber measures Toxicity Index after perfect combustion by burning 100g of specimen.

 

 

Standard:

 

NES 713: Determination Of the Toxicity Index Of the Products of Combustion From Small Specimen of Materials

JB/T 10707: Low-Smoke Halogen-free Thermoplastic Compounds for Flame Retardant Cables

 

 

Feature:

 

1. Observation window made in reinforced plastic allows easy observation of combustion conditions during the test

2. Treating the inside of Chamber with Teflon Coating minimizes chemical reaction with gaseous materials generated in combustion.

3. Door locking device designed for easy opening/closing.

4. Specimen Support for Burner to be located in the center of the combustion mass and for test specimen to be easily loaded

5. Designed for testing in Auto/Manual Mode

6. Auto Ignition for controlling ignition and extinguishment of Gas Burner by Time Device

7. Auto Vent Mode allowing auto release of combustion gases generated in combustion by Time Device

8. Auto Stirrer Mode for complying with conditions of combustion gas stirrer by Time Device specified in the standard Time Device

 

 

Specification:

 

ModelYY435
Size1,185(W)×700(D)×2,100(H) mm
PowerAC 220V, 50/60Hz, 10A
WeightAbout 150kg
InstructionsSupplied
Exhaust50L/s
ToolCompressed air, vacuum cleaners, methane, propane gas (optional)

 

 

Test Result:

 

If 100g of material is burned and the material is diluted in the air of chamber, concentration of each generated gas is given by the following equation.

C × 100 ×V

C8 = --------------- (ppm)

m

C = concentration of gas in test chamber (ppm)

m = fire test mass (g)

V = volume of test chamber (m3)

 

Toxicity Index

 

C81 C82 C83 C8n

Toxicity Index = Σ ------ + ------ + ------ + … + ------

Cf1 Cf2 Cf3 Cfn

1, 2, 3, ... indicates each found Gas.

Cf = concentration of the gas considered fatal to man for a 30 minute exposure time(ppm)

 

Toxicity Constitution& Concentration ( ppm )

Carbon dioxide(CO2) 100,000

Carbon monoxide(CO) 4,000

Hydrogen sulphide(H2S) 750

Ammonia(NH3) 750

Formaldehyde(HCHO) 500

Hydrogen chloride(HCl) 500

Acrylonitrile(CH2CHCN) 400

Sulphur dioxide(SO2) 400

Nitrogen oxides(NO+NO2) 250

Phenol(C6H5OH) 250

Hydrogen cyanide(HCN) 150

Hydrogen bromide(HBr) 150

Hydrogen fluoride(HF) 100

Phosgene(COCl2) 25

Product Tags: smoke density meter   smoke density detector  
Related Products
Email to this supplier
 
From:
Enter your Email please.
To: Dongguan HOOHA Electrical Equipment Company Limited
Subject:
Message:
Characters Remaining: (80/3000)