AC True RMS Digital Earth Resistance Tester 3 Pole 4 Pole Method Measurement
|
|
AC True RMS Digital Earth Resistance Tester 3 Pole 4 Pole Method Measurement
VICTOR 4106A Earth Resistance Tester 3-Pole 4-Pole Method Measurement AC True RMS Large LCD Display With LED Backlight
Basic features of the product Basic measurement functions Earth resistance measurement (RE) Measurement method: 3-pole method, 4-pole method Measuring range: 0.02Ω~1999Ω Minimum resolution: 0.01 Ω Basic accuracy: 5%
Soil resistivity measurement (ρ) Measurement range: 0.01Ω·m~376.8KΩ·m Interval of auxiliary earth rods, setting range: 1.0 m ~ 30.0 m. AC true RMS voltage E.V Measurement range: 0~50V AC bandwidth: 40Hz ~ 200Hz Measurement basic accuracy: 2%
Earth test other features Earth resistance measurement adopts square wave excitation test, the maximum open-circuit voltage is 50Vp-p, and the short-circuit current is <3mA. Automatic range detection in earth resistance measurement. RK resistance test, the line resistance effect can be removed. Earth comparison test, the measurement result can be evaluated by the preset "pass/fail (✓ / ✘)" limit and be given audio alarms accordingly. Product calibration By connecting with the standard instrument, calibrating panel according to the procedures and saving the appropriate calibration data, the periodic calibration is completed and the due accuracy and performance of the product are guaranteed. Large LCD display with white LED backlight. Easy man-machine operation, portable, solid and suitable for field use.
Product basic functions and performance (technical data) (applicable for one year after calibration, 23℃±5℃, 0~70%RH, accuracy = ±(%reading+LSD))
AC voltage E.V
Earth resistance RE (RG when testing ρ)
Soil resistivity (ρ) measurement
General features of the product Operating temperature and humidity 0 to 40ºC (non-condensing ≤10ºC), ≤85%RH Storage temperature and humidity: -20ºC to 60ºC,≤90%RH Working altitude:≤2000m.(Indoor use) Rated transient overvoltage:6K (1.2*50us) I, II, III measurement peak value Withstand voltage:AC8320V(50/60Hz)/5 seconds (between the circuit and the outer box) Insulation impedance:1000MΩ or greater/DC1000V (between the circuit and the outer box) Vibration and shock:Randomness 2g, 5 to 500Hz 1m drop test Calibration period and warm-up time To ensure the accuracy of this table, the calibration period is one year or other The warm-up time after turned on is 10 minutes or other Power supply:Powered by 8 x 1.5 V LR6(AA) alkaline batteries 15V power adapter power supply Automatic shutdown operation: automatic shutdown time 0~90 minutes can be set Size and weight:178 × 110 × 59 (mm), about 600g (including batteries)
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Product Tags: True RMS Digital Earth Resistance Tester 4106A Digital Earth Resistance Tester 4106A digital earth resistance meter | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
AC True RMS Digital Earth Resistance Tester 3 Pole 4 Pole Method Measurement |
|
6V DC Clamp Type Digital Earth Resistance Tester 30A 1300Ω 32mm |
|
VICTOR 4105B intelligent multifunctional grounding testing instrument with High definition LCD display screen |
|
VICTOR 4105A Groundin Resistance tester digital earth tester Insulation Resistance meter |
|
1000V Digital Earth Resistance Tester |
|
CE Digital Earth Resistance Tester 4105a |