Applicable System Voltage Range Up to 800V (AC DC AC&DC)
Auxiliary Power AC 85-265V
Frequency 40-60Hz
Alarm Range 10kΩ-10MΩ
Detailed Product Description
With the development of industrial technology, leakage current brings a great threat to the safety of industrial production. In order to improve the continuity and reliability of power supply, ungrounded power supply system is adopted in many important production sites. AIM-T series industrial insulation monitoring device is mainly used in AC ungrounded system in industrial fields such as mine, glass plant, electric furnace and test equipment, metallurgical plant, chemical plant, explosion dangerous place, computer center and emergency power supply. It is used to real-time monitor the insulation conditicxi of the system to the ground When the grounding fault occurs in the system, it will alarm in time to remind the relevant person to troubleshoot.
 

Main Characteristics

● AC, DC main circuits
● AC/DC main circuits with directly connected DC components, such as rectifiers
● Systems with switch-mode power supplies
● Systems with high leakage capacitances

 

Technical Parameters

Auxiliary powerVoltageAC 85-265V DC 120-370V
Frequency50/60HZ
Insulation monitoringRange of the insulation measurement1k-10M^Ω
Early warning and alarm range10k-10M^Ω
Response time(Ce=luF)<5s
Measuring voltage<50V
Allowable system leakage capacitance<500uF
Internal parametersMeasuring current<270uA
Internal DC impedance>180k^Ω
Power dissipation<8W
Suitable voltage classSystem voltageAC 0~800V DC 0~690V
frequency range40~460HZ
OutputRelay outputError, warning, alarm
EnvironmentWorking temperature(-15 ~ +55℃)
Storage temperature(-20~+70℃)
Relative humidity5%-90%, no dew
Altitude<2500m
CommunicationRS485, Modbus-RTU protocol
Rated impulse voltage/class of pollution8kV/III
EMC electromagnetic compatibility/electromagnetic radiationConform to IEC61326-2-4

 

LCD Display


 