China BLDC Driver Board manufacturer
Changzhou Bextreme Shell Motor Technology Co.,Ltd
Professional BLDC motor products manufacturer and solution supplier!
5
Home > Products > Customized Pumps >

Electric Coolant Customized Pumps 48VDC Input For Immersed Cooling In Data Center

Browse Categories

Changzhou Bextreme Shell Motor Technology Co.,Ltd

City: changzhou

Province/State:jiangsu

Country/Region:china

Tel:86-189-94777701

Contact Person:
Mr.Amigo Deng
View Contact Details

Electric Coolant Customized Pumps 48VDC Input For Immersed Cooling In Data Center

Model Number OWPD650B-1
Place of Origin China
Minimum Order Quantity 5
Price Negotiable
Brand Name Bextremeshell
Supply Ability 1000pcs/month
Packaging Details PE bag+carton
Voltage input 30-60VDC
Power 700W
Working current 15A
Motor Brushless motor
Detailed Product Description

Electric Coolant Pump 48VDC Input for Immersed Cooling in Data Center

 

Product features

Product name:BLDC Electric Water Pump

Model:OWPD650B-1

Service life: 40000hrs

IP grade: IP67

Appearance: Stainless Steel natural color

Bracket: All-in-one

Noise: ≤65dB(A)

Weight: 4.26Kg

Tightness: At 0.4Mpa, the leakage<1ml

Flame retardant: According to GB/T 2408 standard, it meets the horizontal combustion HB level and the vertical combustion V-0 level

Mechanical strength: According to QC/T413-2015 standard, Meets Severity Rating: On Engine

Prohibited substances: Meets GBT 30512-2014

 

The scope of use

Ambient temperature: -40—85℃

Liquid temperature: -40—85℃

Liquid type: Commercial coolants can be used with water pumps, but mixing different coolants is not allowed. The mixing ratio of water and antifreeze is selected in a range of 50/50 to 40/60.

In order for the cooling system to be completely filled with media, the cooling system must be completely drained to a vacuum.

Installation: Vibration and noise requirements must be taken into account in the definition of the installation location and specific fixing elements/fasteners in the application, and the installation position must avoid water accumulation on the surface/inside the connection system.

Typical applications: Energy storage thermal management system, liquid-cooled charging cabinet, data center system

 

Basic parameters:

Rated voltage: 48VDC

Operating voltage range:30-60VDC

Current rating: 15±5% A

Rated performance: 120L/min@180Kpa

Input power: 700W±5%

Maximum flow rate: 180±5% L/min

Maximum head: 23±1 m

Speed range: 2500rpm~5500rpm

Resistance: 2.6±3%Ω

Inductance: Axis-Q 14mH Axis-D 13mH

BEMF: 24.5±3%V

Number of pole pairs: 3 pairs of poles

Insulation rating: F

Electrical strength: <1mA >500MΩ

Harness length: U V W Power cord length 300mm

Plug-in information: Amphenol:AT04-3P-RD01-NFK

 

Instructions for the use of the controller

PCBA dimensions:100mm*90mm,Height:32mm

Controller Installation Dimensions:

Heatsink size:120mm*100mm,Heatsink thickness:8mm


Overall height (including PCBA):42mm,Mounting Sockets:4mm*5mm(Use M3 screws)

 

I/O control port 

  1. PWM. PWM input frequency: 100-1000Hz (200Hz recommended), PWM amplitude: 10-48V, duty cycle speed regulation range description: 0%-10%: pump stop (7% is recommended to stop signal), 11%-55%: pump minimum speed operation; 56%-90%: linear speed range, 91%-100%: maximum speed operation of the pump
  2. Fault. Fault feedback signal output (current type): high level (48V) for normal operation, low level (<1V) for fault, and the typical operating current for fault feedback is 5mA
  3. GND. Signal GND
  4. VSP. Analog voltage input speed regulation(0-10V)
  5. 10V. 10V supply.

  
Pump installation size

The performance of the pump

 


Schematic diagram of test bench

 

Product Tags: 48VDC Customized Pumps   Data Center Customized Pumps   48VDC electric coolant pump  
Related Products
Email to this supplier
 
From:
Enter your Email please.
To: Changzhou Bextreme Shell Motor Technology Co.,Ltd
Subject:
Message:
Characters Remaining: (80/3000)