Input signal | 4~20mADC | Compliance voltage@20mA Model KGP5000:8.6VDC(Input impedance 430Ohm) Model KGP5003:9.6VDC(Input impedance 480Ohm) Split range available |
---|
Transfer characteristics | Linear / EQ / QO / User custom setup (19 points) |
---|
Position transmitter output | 4~20mADC | Power supply 17~31VDC Alarm output *according to NAMUR043 |
---|
Attachment | Linear / Rotary / actuators according to IEC60534-6 VDI/VDE3845 |
---|
Travel range | Linear | 12~250mm *Strokes above 250mm with special kits |
---|
Rotary | 40~100deg |
Action | Single / Double *Pilot relay is available on direct acting only |
---|
Supply pressure | 140~800kPa (1.4~8bar , 20~116psi) |
---|
Enclosure | Housing Protection code Pneumatic connection Electrical connection Mounting threads | Aluminum die-casting with baked acrylic painting IP66 (Common structure) Rc1/4 or 1/4NPT G1/2 , 1/2NPT or M20x1.5 4xM8, 4xM6 |
---|
Weight | 3.0kg(without pressure gauge block), 3.3kg(with pressure gauge
block) |
---|
Operating temperature range | Non-explosion type Explosion type LCD | -40~80degC (-40~176degF) According to each explosion standard -20~70degC (-4~158degF) |
---|
Operating humidity range | 5~95%R.H.(non-condensed) |
---|
Air consumption | Single acting type | 6Nl/min or less@140kPa, 9Nl/min or less@300kPa *at 50% position of full travel |
---|
Double acting type | 16Nl/min or less@400kPa, 20Nl/min or less@550kPa *at balance pressure |
Maximum output capacity | 165Nl/min@140kPa, 290Nl/min@300kPa 370Nl/min@400kPa, 500Nl/min@550kPa |
---|
Accuracy | | Position control | Position transmitter output |
---|
Linearity Hysteresis | +/-1.2%F.S. 0.7%F.S. | +/-1.0%F.S. 0.5%F.S. |
Certificates and approvals | Explosion protection | Ex d IIC T6 Gb:TIIS(JIS), CCC(NEPSI) Ex d IIC T6:KOSHA Ex db IIC T6 Gb:IECEx II 2 G Ex db IIC T6 Gb:ATEX |
---|
CE marking | EMC directive(2014/30/EU) RoHS directive(2011/65/EU) |
HART communication approval | HART7 *Model KGP5003 only |