Unarmoured 1C Power Cable
|
|
5.0.6/1KV Low Voltage Single core Power Cable (Unarmoured) , PVC Insulated Cable according to IEC 60502-1
Application: These cables are used for electricity supply in low voltage installation system, They are suitable for installation in indoors and outdoors, in cable ducts, under ground, in power and switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.
Description:
Construction: Conductors:Copper or Aluminium conductor, round standed or Shaped, Class 2 to IEC 60228, BS EN 60228. For smaller sizes, a solid round conductor, Class 1 as per IEC 60228, BS EN 60228 can also be supplied upon request.
Noted: Insulation color as per standards or customer requirement.
Standard: Basic design to IEC 60502-1, IEC 60228,BS EN 60228 China: GB/T 12706.2-2008 Other standards such as BS7870,DIN and ICEA upon request
Certificates:
Product features: Insulation: PVC Insulation material and thickness shall be as per IEC 60502-1 and BS 6346. PVC material shall be Type A as per IEC 60502-1 or TI1 as per BS EN 50363.PVC Insulation material as per SASO 1694 rated for 85°C continuous operation is also available upon special request.
Colour Code Colour Code (1): Core: Red or Black; 2 Cores: Red, Black; 3 Cores: Red, Yellow, Blue; 4 Cores: Red, Yellow, Blue, Black; 5 Cores: Red, Yellow, Blue, Black, Green; Above 5 Cores: Black Cores with White numerals
Assembly /Inner Sheath: Two, Three or Four insulated conductors are laid-up together with non-hygroscopic fillers and the assembly is bedded with an extruded layer of PVC. In case of non- armoured cables, this layer may be omitted Armour: Aluminum/Galvanized Steel Wires applied helically over the bedding as per IEC 60502 or as per BS 5467, BS 6346. Single core cables shall be Aluminium wire armour. Aluminum/Steel Tapes applied helically over the bedding of multi-core cables as per IEC 60502.
Outer Sheath: Outer sheath shall be of Extruded PVC Type ST2 as per IEC 60502-1 or Type 9 as BS 6346/5467.Special type of PVC sheathing material such as Fire Retardant PVC, Anti-Termite PVC, Anti-Rodent PVC, Sunlight resistant PVC, Oil Resistant PVC are available on special request. Also, special sheathing materials such as LLDPE, MDPE, HDPE, LSF, CPE are available on request.
Fire Performance of Cable Sheaths: Cables can be supplied with special flame retardant PVC outer sheath to comply with the flame test requirements of IEC 60332-3-22, IEC 60332-3-23 and IEC 60332-3-24, can also supply cables with Low Smoke Halogen Free (LSHF) material according to IEC 60502-1, BS 7211, BS 6724 or other equivalent standards.
Parameters: Single core(unarmoured)
Productos show:
Why Choose Zhenglan Cable:
FAQ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Product Tags: pvc insulated flexible cable pvc sheathed power cable LV PVC Insulated Unarmoured Cable |
|
Multicore Flexible Cable PVC Insulated PVC Sheathed IEC60227/BS EN 50525-2-11 3x2.5mm2 H05VV-F |
|
0.6/1KV Low Voltage Copper PVC Insulated Power Cables 1Core for IEC 60502, IEC 60228( CU/PVC) |
|
0.6/1KV Low Voltage Copper PVC Insulated Power Cables 4Core Quadruplex (CV) for IEC 60228; IEC 60227(CU/PVC) |
|
0.6/1KV Low Voltage Copper PVC Insulated Triplex (CV) Power Cables 3 Core for IEC 60228; IEC 60227(CU/PVC) |
|
0.6/1KV Low Voltage Copper PVC Insulated Duplex (CV) Power Cables 2 Core for IEC 60228; IEC 60227(CU/PVC) |
|
Unarmoured 1C Power Cable |