Feed Water Specifications
| Parameter | Specification |
|---|
| FCE (including CO2 and Silica) | < 80 µS/cm |
| Feed Water Source | Condensate water |
| Temperature | 5-45 ℃ (40-113 ℉) |
| Feed pressure | 1.4-7 bar (20-100 psi) |
| Total Chlorine (as CI2) | <0.05 ppm |
| Fe | <0.01 ppm |
| Mn | <0.01 ppm |
| S2- | <0.01 ppm |
| pH | 4-11 |
| Total Hardness (as CaCO3) | <1.0 ppm |
| Dissolved Organics (TOC as C) | <0.5 ppm |
| Silica (SiO2) | <1.0 ppm |
Typical Module Performance
| Parameter | Specification |
|---|
| Typical Recovery | >85% |
| Maximum Feed Pressure | 7 bar (100 psi) |
| Maximum Feed Temperature | 45 ℃ (113 ℉) |
| Minimum Discharge pressure | > 1 bar |
| DC Voltage* | 0-300 V |
| DC Amperage | 0-6 A |
| Product Resistivity | >10 MΩ·cm |
| Silica (SiO2) Removal | 90-99% depending on feed water |
*Voltage required depends on module size
The information provided in this brochure contains general
descriptions or performance characteristics that may not always
apply as described in actual use cases or may change due to further
product development. An obligation to provide the respective
characteristics shall only exist if expressly agreed upon in the