XHDD 503C Cable Faults Pin-pointer
Product Description
XHDD503 C The cable fault locating instrument is used to determine
the fault point of power cable by acoustic and magnetic synchronous
method. With the help of the shock discharge generator to generate
electronic flasover, picked up and amplified by the corresponding
probe, by auditory and visual judgment, to determine the exact
location of the fault point, complete the precise positioning of
the cable fault point within the rough measurement range of the
equipment, set the acoustic magnetic time difference positioning
technology, path assisted testing and other technologies in one,
provide a variety of test modes and a variety of tips. Efficiently
and accurately locate cable faults.
Features
1, 5 inch touch bright LCD, ensure visible in the sun.
2, the use of acoustic magnetic synchronous positioning technology,
automatic calculation of acoustic magnetic time difference.
3, the gain value and trigger value of the acoustic signal and
magnetic signal are manually adjusted to adapt to a variety of
environmental fixed points.
4, with background noise reduction technology, you can choose a
variety of filtering methods.
5, with BNR background noise reduction and mute noise reduction
function.
6, with path deviation indication.
7, equipped with multi-layer physical isolation signal sensor,
waterproof class IP65.
8, built-in large capacity lithium battery, long standby time, with
fast charger.
9, compact and light, easy to operate, easy man-machine interface.
All pass | 100Hz~1600Hz |
Low pass | 100Hz~300Hz |
High pass | 160Hz~1600Hz |
Band pass | 200Hz~600Hz |
Maximum signal gain | >=112dB |
Fixed point accuracy | 0.2m |
Battery | 4*18650 standard lithium battery |
Use time | Continuous use time > 8 hours |
Charging time | <6 hours. |
Ambient temperature | -10℃-55℃, humidity 5-90%RH, altitude <4500m. |