Integrated Gas Fire Suppression Systems With No Power Required For Data Centers

Integrated Gas Fire Suppression Systems With No Power Required For Data Centers

Price USD480-520/set
Filling density ≤1150 kg/m3
Model Number JGQ2/1.6-XJ
Minimum Order Quantity 1 set system
Delivery Time 15-20days
Payment Terms T/T,L/C
Container capacity 2 L
Max working pressure 2.5 Mpa
Storage pressure 1.6 Mpa
Certification GSG\TUV\ I S O 9 0 0 1, 1 4 0 0 1, 4 5 0 0 1
Supply Ability 30000set/month
Dimensions 745×425×42 mm
Place of Origin Guangzhou,China
Brand Name XINGJIN
Packaging Details Wooden Box Or Plywood Outer Box With Bubble Bag Or Paper
Detailed Product Description

1. Product Introduction

The Server-Rack Fire Suppression Unit is an innovative automatic fire suppression system independently developed by our company. It is specifically designed for protecting equipment cabinets and enclosures. This unit is also known as a temperature‑sensing detection and extinguishing integrated device or a pre‑engineered fire extinguishing unit.

The unit integrates the following components into a single, self‑contained assembly:

  • Fire extinguishing agent storage vessel

  • Delivery piping and discharge nozzle

  • Enclosure housing

  • Pressure indicator

  • Fire detector(s)

  • Signal feedback device

One Server-Rack Fire Suppression Unit can protect a single equipment cabinet or, depending on the configuration, multiple cabinets within a defined enclosure.

Fire Extinguishing Agent Options

The device can be charged with either of the following clean agents:

  • HFC-227ea (FM200)

  • FK-5-1-12 (Novec 1230)

Both FM200 and Novec 1230 are clean gas extinguishing agents that operate primarily through chemical fire suppression, supplemented by physical cooling effects. They are colourless, odourless, low‑toxicity, non‑conductive, and leave no residue on protected equipment. They will not cause damage to property or precision facilities. With relatively low extinguishing concentrations, they provide reliable suppression for Class B fires, Class C fires, and electrical fires.

Detection Technology

The Server-Rack Fire Suppression Unit incorporates two independent detection methods:

  1. Temperature‑sensing glass bulb

  2. Fire detection tube

This design eliminates the need for a conventional fire detection system comprising smoke detectors, heat detectors, and a separate fire control panel. Our integrated approach offers the following benefits:

  • Enhanced detection and extinguishing performance

  • Better adaptability for installation within equipment cabinets

  • Reduced space requirements

  • No interference with existing cabinet components or airflow


2. Applications

The Server-Rack Fire Suppression Unit is suitable for the following applications:



Industry/ApplicationCabinet/Equipment Type
IT & Computer SystemsServer cabinets, data storage racks
Telecommunications & CommunicationsTelecom server cabinets, transmission equipment racks
Banking & FinanceBank equipment control cabinets
Industrial & MechanicalControl cabinets across various industries and sectors

3. Working Principle

The Server-Rack Fire Suppression Unit offers two temperature‑base0d activation modes:

Mode 1: Temperature‑Sensing Glass Bulb

When the ambient temperature inside the protected enclosure reaches the rated activation temperature of the glass bulb (standard setting: 68°C, with other temperature ratings available upon request), the bulb bursts instantly. This opens the agent release port, and the stored gas extinguishing agent is immediately discharged through the nozzle. The agent cools the protected area and suppresses the fire.

Mode 2: Fire Detection Tube

When the detection tube is exposed to a heat source and reaches its activation temperature (160°C ± 10°C), the pressurised gas inside the tube expands rapidly. The tube then ruptures at the point of highest temperature (the fire origin). This pressure drop activates the storage vessel, and the extinguishing agent is discharged through the rupture point of the tube, providing localised cooling and fire suppression.

4  Main technical parameters and characteristics

4.1 Model and specifications of server-rack fire suppression unit

   

Specification

Size L*W*H (mm)

Volume of storage container(L)

Filling density(kg/m3)

Storage pressure(MPa)

Max working pressure

(50℃; MPa)

Applicable ambient

JGQ2/1.6-XJ

745×425×42

2

1150

1.6

2.5

0℃--50℃

 

 

4.2 Technical parameters of fire detecting tube

Outer diameter

Inner diameter

Thickness

Fusion Point

Φ6mm

4mm

1mm

160℃±10℃