SPIIT13 Infi Net To Infi Net Local ABB Module
|
PRODUCT DETAILS The connection to the CS31 system bus is made by meansof a 3-pole detachable terminal block. Please observe: 1.All of the AC31 devices, no matter whether they are master or slave devices, are connected with twistedpair bus line as follows:One core of the bus line is looped through via the BUS1 terminals of all devices to be connected to the CS31 system bus. The other core of the bus line is looped through via the BUS2 terminals of all devices to be connected to the CS31 system bus. 2.If the basic unit 07 KT 97 is located at the beginning or at the end of the bus line, the bus terminating resistor (120 W) has to be connected additionally between the BUS1 and BUS2 terminals. 3.The shield of the twisted-pair bus line is looped through via the SHIELD terminals of all the devices to be connected to the CS31 system bus.
|
||||||||||||||||||||||||||||||||||||||||