China Oil Purifier manufacturer
Chongqing Gold Mechanical Equipment Co.,Ltd.
We mainly design and manufacture the petroleum testing instrument and electrical testing instrument.
8
Home > Products > Other Electrical Testing Instrument >

GDVA-405 220V to 500kV Power Transformer Analyzer, Automatic CT PT Analyzer

Browse Categories

Chongqing Gold Mechanical Equipment Co.,Ltd.

City: chongqing

Province/State:chongqing

Country/Region:china

Tel:86-23-62984892

Contact Person:
Mr.Tina Chen
View Contact Details

GDVA-405 220V to 500kV Power Transformer Analyzer, Automatic CT PT Analyzer

Brand Name GOLD
Model Number GDVA-405
Place of Origin Chongqing, China
Minimum Order Quantity 1 set
Price Low price
Payment Terms D/A, L/C, D/P, T/T, Western Union, MoneyGram
Supply Ability 10000 sets/month
Delivery Time 7 days
Packaging Details GDVA-405 220V to 500kV Power Transformer Analyzer, Automatic CT PT Analyzer packed in veneer case
Item Name GDVA-405 220V to 500kV Power Transformer Analyzer, Automatic CT PT Analyzer
Application Analysis power transformer, current transformer or voltage transformer
Test standards IEC60044-1, IEC60044-6
Features High Quality Touch Screen 500kV Power Transformer Testing Equipment
Device Best design Power, Current Transformer Testing Equipment
Test object 220V to 500kV Transformer
Packaging dimensions 70*50*41cm
Gross weight 40kg
Power supply 220V 50Hz
Warranty period 1 year
Voltage measurement range 0~200 V
Turns ratio measurement range 1~35000
Data saved >1000groups
Detailed Product Description

GDVA-405 220V to 500kV Power Transformer Analyzer, Automatic CT PT Analyzer

 

Functions:

Tests for Current Transformer:

  • Excitation curve and parameters test
  • Turns ratio test
  • Ratio and phase error test
  • Polarity mark check
  • Winding resistance measurement
  • Secondary loop burden measurement
  • Error line curve test for protection CT
  • Transient CT parameters test
  • CT nameplate guess
  • Saturation hysteresis loop curve measurement
Tests for Potencial Transformer:
  • Turns ratio test
  • Ratio error and phase angle error test
  • Polarity test
  • Secondary burden test
  • Winding resistance test
Applications:
  • CT nameplate check
  • CT parameters check in work burden
  • CT transient parameters analysis
  • CT ratio and phase error calibration
  • PT routine test
 
Specifications:
No.Item NameGDVA-405 220V to 500kV Power Transformer Analyzer, Automatic CT PT Analyzer
1Test standardsIEC60044-1, IEC60044-6, GB1208, GB16847, C57.13
2Power supplyAC220V±10%,50Hz/60Hz±10%
3Power output0.1~180V (AC)
4Current output0.001~5A(RMS)
5Power output300VA
6Max. knee voltage measurement45kv
7Current measurement range0~10A (automatically change range in 0.1/0.4/2/10A)
8Current measurement error<±0.1%+0.01%FS
9Voltage measurement range0~200 V (automatically change range in 1V/10V/70V/200V)
10Voltage measurement error< ±0.1%+0.01%FS
11Turns ratio measurement range

1~35000;

1~2000 error<0.05%;

2000~5000 error>0.1%;

5000~35000 error<0.2%

12Phase measurementerror:±2min,resolution:0.01min
13Coil resistance measurement

Range: 0~8kΩ(automatically change range in 2ohm /20ohm /80ohm/800ohm/8kohm)

Error< 0.2%RDG+0.02%FS

Maximum resolution: 0.1mΩ

14Temperature measurement-50~100 Celsius degree, error<3 Celsius degree
15CT Secondary burden

Range 0-160ohm (automatically change range in 2ohm/ 20ohm/80ohm/160ohm)

Error <0.2%RDG+0.02%FS

Maximum resolution 0.001ohm

16PT Secondary burden

Range 0-80kohm (automatically change range in 800ohm / 8kohm /80kohm)

Error <0.2%RDG+0.02%FS

Maximum resolution: 0.1ohm

17PT ratio measurement

Range :1~35000,

1~5000 error<0.2%

5000~35000 error<0.5%

18Saved data groups>1000groups
19Work conditionTemperature:-10℃-50℃, moist:≤90%
20Size485mm×356mm×183mm
21Weight<15Kg

 