Wire And Cable Heat Release Test Device
|
DIN EN 50399:2017 Wire and Cable Heat Release Test Device with Stainless Steel Two-Way Speed ProbeProduct introduction EN 50399 specifies the apparatus and methods of test for the assessment of vertical flame spread, heat release and smoke production of vertically-mounted bunched wires or cables, electrical or optical, under defined conditions. EN 50399 details the apparatus and the arrangement and calibration of the instrumentation to be installed in order to measure the heat release and the smoke production during the fire test. Test procedures to be used for type approval testing for classification of cables in Euroclasses B1ca, B2ca, Cca and Dca are given. Technical Parameters 1.Test chamber has the dimension of 1,000±100(W) x 2,000±100(D) x
4,000±100(H) mm. The bottom surface of the test chamber is higher
than the ground while the rear side is supplemented with insulated
material to insulate it from heat. Features and Application 1. Standard 19 cabinet unit, including paramagnetic O2,
non-dispersive infrared CO2 gas analyzer; Application:The test system is a medium-scale fire test simulating bundled cable or fiber optic cable. The test cable is installed on a vertical standard steel ladder and ignited by a specified ignition source to evaluate the combustion behavior and combustion performance of the cable. Combustion performance data for the early stages of a cable fire, The test of the heat release rate reflects the danger of the flame spreading along the cable and the potential impact of the fire source on the adjacent area. The smoke density test shows the visibility of the fire area and the danger of the smoke to the personal safety. Product Details of the Wire and Cable Heat Release Test Device EN 50399 Test apparatus is consist of IEC 60332-3 apparatus, heat
release measurement, smoke density measurement and modified air
inlet system. This is accomplished by fitting a small instrumented
section of ducting into the exhaust system of the rig and using
this with associated gas analysis instrumentation and software. The
duct section houses all gas sampling probes, temperature and mass
flow probes and has ports for the smoke measuring system. Standards DIN:DIN EN 50399:2017 Installation requirements Electrical: 110V AC 60Hz / 230V AC 50Hz, 5A Bunched Cable Vertical Flame Tester.pdf |
Product Tags: flammability test apparatus flammability testing labs |
![]() |
ISO 5660 AC220V Cone Calorimeter For Building Materials Testing |
![]() |
IEC 60331 Cable Circuit Integrity Fire Resistance Test Machine BS 6387 Cable Fire Resistance Test Equipment |
![]() |
UL910 Steiner Tunnel Furnace chamber |
![]() |
PC control model ISO 5657 Building Materials Ignitability Flammability Tester |
![]() |
ISO 5657 Building Materials Ignitability Flammability Tester |
![]() |
ISO 9150/BS EN 348 Protective Clothing Molten Metal Splashes Impact Resistance Tester |