China Lab Testing Equipment manufacturer
SKYLINE INSTRUMENTS CO.,LTD
Skyline Instruments Co.,LTD We only manufacture Lab Testing Equipment
9
Home > Products > Building Materials Flammability Tester >

Building Materials Flammability Tester Critical Radiant Flux Flammability Testing Equipment

Building Materials Flammability Tester Critical Radiant Flux Flammability Testing Equipment

Brand Name SKYLINE
Model Number SL-FL086
Certification Calibration Certificate
Place of Origin China
Minimum Order Quantity 1 unit
Price neogitable
Payment Terms T/T, Western Union, MoneyGram
Supply Ability 1 unit / month
Delivery Time 20 working days
Packaging Details Plywood case
SKYLINE Flooring Radiant Panel Test Apparatus
Standards EN ISO 9239-1, ASTM E648, ASTM E970, NFPA 253
Heat flux measurement range (0-15) Kw / m2
Exhaust speed (2.5 ± 0.2) m / s
Gas flow rate (0.026 ± 0.002) L / S
Flame height 60 ~ 120mm
Detailed Product Description

Critical Radiant Flux Flammability Testing Equipment For Flooring Panel

 

Application

It is used to measure the burning of materials through a certain degree of heat radiation and flame environment. It is used in various kinds of floor materials such as textile carpet, cork board, wood board, rubber board, plastic floor and floor coating material Case of the critical heat radiation value. The EU uses this test method to classify fire protection material for all European Union member countries.

 

Features
1. All structural components are made of stainless steel, appearance,and corrosion resistance;
2. The radiation source is a porous ceramic heat radiating plate of 300mm*450mm, and tilted 30 °;
3. The calorimeter is imported from United States , range 50kW/m2;
4. The igniters diameter is 0.7mm, 19/EA, is located at the bottom of the center line of each 60°;
5. The standard plate is made of calcium silicate without coating layer,which is size of 1050*250mm and thickness is 20±1mm ,density is 850 ± 100kg/m³;
6. Small stainless steel auxiliary ignition burner ignited sample.
7. Inlet flow control valve, precise control of propane flow;
8. Equipped with air blower providing air, mixed gas through the venturi mixing gas

 

Standards
• ISO 9239-1: Flooring fire reaction test - Part 1: Combustion performance of flooring materials tested by radiant heat
• ISO 9239-2: Flooring fire reaction test - Part 2: Testing flame spread status under the heat flux is 25kW/m2
• ASTM E 648: Critical Radiant Flux of Floor standard test - covering system uses radiant heat energy
• ASTM E 970: Using a Radiant Heat Energy Source, test insulation floor insulation standard test for Critical Radiant Flux Using a Radiant Heat Energy
• NFPA 253: Standard Test Method for using radiant heat energy, test plates overlay system Critical Radiant Flux

 

Technical parameters

 Maximum operating power 5kw
 Timing accuracy <1s / h
 Heat flux meter Measuring range

 (0-15) Kw / m2; (heat flow customer-owned)

 

 Heat flux meter accuracy ± 0.2Kw / m2
 Heat flux meter accuracy <± 3%;
 Heat radiation pyrometer range 400-600 ℃, the accuracy of ± 0.5 ℃;

 

 Black body temperature error ± 5 ℃;
 Smoke speed (2.5 ± 0.2) m / s
 Smoke capacity (39-85) m3 / min
 Porous refractory radiation board size 300mm × 450mm, the ability of about 900 ℃ high temperature;

 

 Thermocouple diameter of 3.2mm K-type stainless steel armored thermocouple
 Burning torch diameter ¢ 10mm diameter ¢ 6mm, spray tube on the 35 ¢ 0.7mm hole
 Flame height 60 ~ 120mm adjustable
 Ignition system high voltage electronic ignition
 Burning box size L1420 * W1200 * H2300 (mm)
 Strong exhaust system the machine is equipped with a strong fan, when the test is completed, start the exhaust fan system will be exhausted outdoors

 

Product Tags: horizontal flammability tester   vertical flammability chamber  