A multi-function range
>> Type D: Distribution switchboards up to 6300 A
>> Type DC: Power factor correction column
>> Type Mf: Fixed-type motor-control centres up to 6300 A
>> Type Mw: Withdrawable-type motor-control centres up to
6300 A
>> Type Ms: Variable-speed drives and starters column
>> Type C: Cubicles up to 630 A.
Electrical and Mechanical Characteristics
| Application | D | Dc | C |
| 132Type | 132type | 134Type |
| Rated voltage |
| Rated insulation voltage (V AC) | 1000V |
| Rated operating voltage(V AC) | 690V |
| Rated impulse withstand voltage | 12KV |
| Overvoltage category | IV |
| pollution degree | 3 |
| Frequency | Up to 400HZ |
| Rated Current | |
| |
| |
Main busbars | Single busbars | Double busbars | |
| Rated current A | Up to 4000A | Up to 6300A | |
| Rated peak withstand current KA | 63/105/187KA | 220KA | |
| Rated short time current KA rms/1s | 30/50/85 | 100 | |
| | | |
| | | |
| Distribution busbars | | |
| Rated current | Up to 3200 | | 630 |
| Rated peak withstand current KA | 63/105/187 | | 40/53 |
| Rated short time current KA rms/1s | 30/50/85 | | 20/25 |
| Application | Mf | Mw | Ms |
| 132Type | 132type | 134Type |
| Rated voltage |
| Rated insulation voltage (V AC) | 1000V |
| Rated operating voltage(V AC) | 690V |
| Rated impulse withstand voltage | 12KV |
| Overvoltage category | IV |
| pollution degree | 3 |
| Frequency | Up to 400HZ |
| Rated Current | |
| |
| |
Main busbars | Single busbars | Double busbars | |
| Rated current A | Up to 4000A | Up to 6300A | |
| Rated peak withstand current KA | 63/105/187KA | 220KA | |
| Rated short time current KA rms/1s | 30/50/85 | 100 | |
| |
| Distribution busbars | | |
| Rated current | Up to 3200 | 1000A | Up to 3200 |
| Rated peak withstand current KA | 63/105/187 | 187 | 63/105/187 |
| Rated short time current KA rms/1s | 30/50/85 | 85 | 30/50/85 |