The 1746-IV32 is an SLC 500 32 Channel Digital Input Module by AB.
It is a 24V DC current sourcing input module with 32 inputs and 8
points per fused common that is fixed in any slot of the SLC 500
chassis. It has an operating voltage range between 15 and 30V DC at
50 °C and a range of 15 and 26.4V DC at 60 °C and it has a
backplane draw current of 0.05A at 5V DC. The 1746-IV32 has a
non-replaceable electronically-fused common with the fuse rated at
2.5A and it provides a 60s 1500V AC-tested isolation from the
backplane. The signal delay on the input points has a maximum delay
time of 3ms for both the ON and OFF states and the module has a
maximum OFF-state current of 1.5mA. It also has a minimum ON-state
voltage of 15V DC and a maximum OFF-state voltage of 5V DC. It has
a nominal input current of 5.1mA per point and the maximum heat
dissipation on each point is 0.2W with an aggregate of 6.65W for
the whole module. The 1746-IV32 is CE, CSA, and UL-certified and it
provides NEMA standard ICS 2-230 Noise immunity. It is designed and
tested to withstand a working vibration of 2.5G at 57-200Hz with a
tested peak displacement of 0.015 inches and maintains an optimal
function even with an operational shock of 30G. It has a working
temperature between 0 and 60 °C at a relative humidity range of
5-95%.
The AB 1746-IV32 is a Discrete Input module that is a component
module of the SLC 500 product range. This module is a 24 Volt DC
sourcing input module, with thirty-two (32) input channels grouped
into four (4) of eight (8) channels each.
Each channel of this module operates at a voltage range of 15 to 30
Volts DC at 50 degrees Celsius and 15 to 26.4 Volts DC at 60
degrees Celsius. It has a backplane current consumption of 0.050
Amperes @ 5 Volts DC and 0 Amperes @ 24 Volts DC with a channel
isolation from backplane of 1500 Volts AC for 1 minute.
The module’s channels have a maximum signal delay of 3 milliseconds
for both On and Off transition. The minimum on-state voltage is
15.0 Volts DC while the maximum off state voltage is 5.0 Volts DC
and maximum off-state current is 1.5 milliamperes. The nominal
input current to this module is 5.1 milliamperes at 24 Volts DC. It
has an individual channel heat dissipation of 0.20 Watts and total
heat dissipation of 0.25 Watts.
The 1746-IV32 is available in four (4) series - specifically,
Series A, B , C and D. Series A, B, and C come with a fuse per
input common which means that four (4) internally installed,
non-replaceable fuses are integral to this series. Series D modules
do not have internal group fusing.
The 1746-IV32 may be installed to any SLC 500 chassis. Similarly,
it can be used as input module of any SLC 500 processor. It may
also be installed in a local I/O rack, extended rack, and
distributed I/O rack.