Block Type: CatalogNumbers: Output Block, Normally–Closed Relays TerminalAssemblyonly
ElectronicsAssemblyonly Output Block, Normally-Open Relays TerminalAssemblyonly ElectronicsAssemblyonly | 16 circuit relay outputs in four isolated groups of four IC660BBR100 IC660TBR100 IC660EBR100 IC660BBR101 IC660TBR101 IC660EBR101 |
Size (height x width x depth): Weight LEDs (I/O Block) LEDs (each circuit) | 8.83” (22.44cm) x 3.50” (8.89cm) x 3.94” (10.00cm) 4 lbs. (1.8 kg) UnitOK,I / OEnabled Individual relay coilstate |
EnvironmentalSpecifications: Operatingtemperature Storagetemperature Humidity Vibration | 0C to +60C (32F to +140F) –40C to +100C (–40F to +212F) 5 to 95% (non–condensing) 5–10Hz 0.2” (5.08mm) displacement; 10–200Hz at 1G |
Block PowerSupply: Frequency Operatingvoltage Power requirement Power supplydropouttime Isolation: Alloutputs to chassis ground Between output groups Power terminals to chassis ground Power terminals to outputs Comms terminals to power terminals Comms terminals to outputs HeatDissipation | 47–63 Hz (115VAC) 93VAC to 132VAC; (230VAC) 185VAC to 265VAC 87mA at 115 VAC 1 cycle 1500 VAC 1500 VAC 1700 VDC 1500 VAC 1700 VDC 1500 VAC 10.1 watts maximum with 16 outputs on |
OutputCharacteristics: Maximum Output current Maximumswitchingpower Maximuminrush current
Output OFF leakage current Maximumswitchingfrequency Output turn–on delay (maximum) Output
voltage range Minimumrecommendedload | 2 amps per circuit 60 Watts or 125 VA 2 amps per circuit 0.1mA 20cycles / minute(inductiveloads) 5mS 5V to 250V AC or 5V to 220V DC 10mA |
Relay Type Initial Contact Resistance | Fixed coil moving armature 100 milliohms, maximum |
Typical Life: OperatingVoltage: 250VAC 250VAC 125VAC 220VDC 110VDC 30VDC 30VDC 12VDC | MaximumCurrent for Load Type *TypicalLife ResistiveLampSolenoid(operations) 0.5A –– –– 200,000 ––0.1A0.1A100,000 1.0A0.2A0.3A100,000 0.3A––––100,000 0.6A––––100,000 2.0A––––500,000 ––0.2A0.3A100,000 ––0.3A0.5A100,000 |
Effect of AdditionalCurrent onOperatingLife: 250VAC 125VAC 30VDC 12VDC | Current in Load TypeTypicalLife ResistiveLampSolenoid(operations) 0.1A –– –– 1,500,000 0.3A––––1,000,000 1.0A––––2,000,000 2.0A––––1,000,000 * Lamp loads are defined as a X10 inrush with a power factor (PF)
of 1.00; when turned OFF, they represent a PF of 1.00. Solenoids
are de- fined as a X10 inrush with a PF of 0.65; when turned OFF,
they repre- sent a PF of 0.35. |