Allen Bradley PLC-5 Processor Module Controller 64K 1785-L60B Series E
|
Detailed Product Description
Allen Bradley PLC-5 Processor Module Controller 64K 1785-L60B Series E
Technical specifications: Backplane Current PLC-5/11, -5/20, -5/30: 2.3A @ 5Vdc PLC-5/40, -5/40L, -5/46, -5/60, -5/60L, -5/80, -5/86: 3.3A @ 5Vdc Isolation Voltage Communication Ports - tested to 500V for 60
seconds Relay Cartridge - tested to 1000V for 60 seconds Operating Temperature IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0-60o C (32–140o F) Storage Temperature IEC 60068-2-1 (Test Ab, Un-packaged
Non-operating Cold), IEC 60068-2-2 (Test Bc, Un-packaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock): –40 to 85o C (–40 to 185o F) Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged
Non-operating Damp Heat): 5–95% non condensing Vibration IEC60068-2-6 (Test Fc, Operating): 2g @10–500Hz Shock IEC60068-2-27:1987, (Test Ea, Unpackaged shock): Operating - 30g Non-operating - 50g Emissions CISPR 11: Group 1, Class A (with appropriate enclosure) ESD Immunity IEC 61000-4-2: 4kV contact discharges Radiated RF Immunity IEC 61000-4-3: 10V/m, with 1kHz sine-wave 80% AM from 30MHz to 1000Mhz EFT/B Immunity IEC 61000-4-4: +2kV at 5kHz on communications ports Surge Transient Immunity IEC 61000-4-5: +2kV line-earth(CM) on communications ports Conducted RF Immunity IEC 61000-4-6: 10Vrms with 1kHz sine-wave 80%AM from 150kHz to 30MHz Enclosure Type Rating None (open style) Time-of-Day Clock/Calendar1 Maximum Variations at 60× C: ± 5 min
per month Typical Variations at 20× C: ± 20 s per month Timing Accuracy: 1 program scan Available Cartridges 1785-RC Relay Cartridge Battery Allen-Bradley 1770-XYC Memory Modules • 1785-ME32 • 1785-ME64 • 1785-M100 I/O Modules Bulletin 1771 I/O, 1794 I/O, 1746 I/O, and 1791 I/O
1 Regardless of this switch setting, outputs are turned off when
any of the following occurs: - controller detects a runtime error - an I/O chassis backplane fault occurs - you select program or test mode - you set a status file bit to reset a local rack 2 If an EEPROM module is not installed and controller memory is
valid, the controller's PROC LED indicator blinks, and the processor sets S:11/9, bit 9 in the major fault status
word. To clear this fault, change the controller from program mode to run mode and back to program mode. 3 If the controller's keyswitch is set in REMote, the controller
enters remote RUN after it powers up and has its memory updated by the EEPROM module. 4 A processor fault (solid red PROC LED) occurs if processor mem
Contact person: Anna E-mail: wisdomlongkeji@163.com Cellphone: +0086-13534205279 Similar Products
This equipment is sensitive to electrostatic discharge that can
cause internal damage and affect normal operation. Follow these
guidelines when you handle this equipment: • touch a grounded object to discharge potential static • wear an approved grounding wrist strap • do not touch connectors or pins on component boards • do not touch circuit components inside the equipment • if available, use a static-safe workstation • when not in use, store the equipment in appropriate static-safe
packaging
• This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes
up to 2000 meters without derating. • This equipment is considered Group 1, Class A industrial
equipment according to IEC/CISPR Publication 11. Without
appropriate precautions, there may be potential difficulties
ensuring electromagnetic compatibility in other environments due to
conducted as well as radiated disturbance. • This equipment is supplied as "open type" equipment. It must be
mounted within an enclosure that is suitably designed for those specific environmental conditions that will be
present and appropriately designed to prevent personal injury
resulting from accessibility to live parts. The interior of the
enclosure must be accessible only by the use of a tool. Subsequent
sections of this publication may contain additional information
regarding specific enclosure type ratings that are required to
comply with certain product safety certifications. NOTE: See NEMA Standards publication 250 and IEC publication 60529,
as applicable, for explanations of the degrees of protection provided by different types of enclosure.
Also, see the appropriate sections in this publication, as well as the Allen-Bradley publication 1770-4.1
("Industrial Automation Wiring and Grounding Guidelines"), for
additional installation requirements pertaining to this equipment.
|
|||||||||
Product Tags: analog interface module diode redundancy module |
Related Products
![]() |
3BSE000863R0001 SR511 POWER REGULATOR MODULE 310 W MAX 35 AMP 18-30 VDC INPUT 5 VDC OUTPUT |
![]() |
Honeywell TK-FXX102 Redundant Power Supply Module 10SLOT Coated 5.1VDC - 24VDC |
![]() |
Honeywell TC-ODJ161 Output Module Isolated Discrete 16 Point 24 VDC |
![]() |
EMERSON FISHER ROSEMOUNT 01984-1137-0001 POWER SUPPLY I/O PCB BOARD MODULE |
![]() |
AO801 Analog Input Output Module 3BSE020514R1 ABB 20mA 12 Bit RLmax 850 Ohm |
![]() |
ABB AC 800F TK808F Supply Cable 3BDM000211R1 115/230 VAC Euro Plug 2 M |
Email to this supplier