ABB AI835A S800 Analog Input Module 3BSE051306R1 8 channels I/O
Module AI835 3BSE008520R1 AI835A 3BSE051306R1 Description of AI835/AI835A : The AI835/AI835A provides 8 differential input channels for
Thermocouple/mV measurements. Measurement ranges configurable per
channel are: -30 mV to +75 mV linear, or TC Types B, C, E, J, K, N,
R, S and T, for AI835A also D, L and U. One of the channels (Channel 8) may be configured for “Cold
Junction” (ambient) temperature measurements, thus serving as
CJ-channel for Ch. 1...7. The junction temperature may be measured
locally on the MTUs screw terminals, or on a connection unit
distant form the device. Alternatively, a fix junction temperature for the module may be set
by the user (as parameter) or for AI835A also from the application.
Channel 8 may be used in the same manner as Ch. 1...7 when no
CJ-temperature measurement is needed. General Information Type | Analog Input | Signal specification | -30..75 mV linear; TC types B, C, D, E, J, K, L, N, R, S, T and U | Article number | 3BSE051306R1 | Number of channels | 8 | Signal type | See table in S800 Modules and Termination Units, 3BSE020924 | HART | No | SOE | No | Redundancy | No | High integrity | No | Intrinsic safety | No | Mechanics | S800 |
I/O Modules AI801 | AI810 | AI815 | AI820 | AI825 | AI830A | AI835A | AI843 | AI845 | AI880A | AI890 | AI893 | AI895 | AO801 | AO810V2 | AO815 | AO820 | AO845A | AO890 | AO895 | DI801 | DI802 | DI803 | DI810 | DI811 | DI814 | DI818 | DI820 | DI821 | DI825 | DI828 | DI830 | DI831 | DI840 | DI880 | DI890 | DO801 | DO802 | DO810 | DO814 | DO815 | DO818 | DO820 | DO821 | DO828 | DO840 | DO880 | DO890 | DP820 | DP840 |
Detailed Data: Resolution | 15 bits | Input impedance | > 1 MΩ | Isolation | Groupwise isolated from ground | Error | Max. 0.1% | Temperature drift | Typ. 5 ppm/°C, Max. 7 ppm/°C | Update cycle time | 280 + 80 * (number of active channels) ms at 50 Hz; 250 + 70 *
(number of active channels) ms at 60 Hz | Maximum field cable length | 600 meters (656 yards) | CMRR, 50Hz, 60Hz | 120 dB | NMRR, 50Hz, 60Hz | > 60 dB | Rated insulation voltage | 50 V | Dielectric test voltage | 500 V a.c. | Power dissipation | 1.6 W | Current consumption +5 V Modulebus | 75 mA | Current consumption +24 V Modulebus | 50 mA | Current consumption +24 V external | 0 |
Diagnostics Front LED’s | F(ault), R(un), W(arning) | Supervision | Module error´: reference channels, power supply low Channel error: open-circuit CJ-channel (ch 8): < -40 °C (-40°F) and > 100 °C (212°F) | Status indication of supervision | Module Error, Module Warning, Channel error (8) |
Features and benefits - 8 differential input channels for thermocouple/mV.
- Channel 8 can be designated as the CJ-channel (4-wire Pt100 RTD)
- Variety of thermocouples with the following characteristics: B, C,
E, J, K, N, R, S and T for AI835A also D, L and U
- 15 Bit resolution (A/D)
- Inputs are monitored for wire-break open-circuit
Compability Use with MTU | TU810, TU812, TU814, TU818, TU830, TU833 | Keying code | BA |
Dimensions Height | 119 mm (4.7”) | Width | 45 mm (1.77”) | Depth | 102 mm (4.01”), 111 mm (4.37”) including connector | Weight | 0.22 kg (0.49 lbs.) |
Terminal: TU814V1 | TU810V1 | TU833 | TU838 | TU812V1 | TU850 | TU830V1 |
Picture of AI835A
Some ABB items sold by WTL:
Liability: WTL is not liable for any personal injury or property damage
resulting from the use of this equipment. It is buyer's responsibility as to the safe handling & operation of
this equipment and to verify equipment is compliance to their machinery.
Our Brands: 【Honeywell】 | Module DCS/PLC/Transmitter | 【Emerson/Delta V】 | Module/ CT Motor & Drives | 【ABB】 | I/O Module | 【AB】 | Module&Touch Screen | 【Rosemount】 | Transmitter | 【Yokogawa】 | Transmitter | 【Yaskawa】 | Servo Drive&Servo Motor | 【GE/Fanuc】 | IC69 Series PLC | 【Mitsubishi】 | Servo Drive&Servo Motor |
(Modicon,SMC,SICK,NORGREN,Siemens,Ebmpapst etc.)
|