Parameter | Description |
Input Span Adjustment Range | No limits to adjustments within the maximum range except minimum
span limit of 1 engineering unit |
Analog Output Digital Communications: | Two-wire, 4 to 20 mA (HART & DE Transmitters only) Honeywell DE, HART 7 protocol or FOUNDATION Fieldbus ITK 6.1.2
compliant All transmitters, irrespective of protocol have polarity
insensitive connections. |
Output Failure Modes (HART/DE only) |
Honeywell
Standard:
NAMUR NE 43 Compliance: Normal Limits: 3.8 – 20.8 mA
3.8 – 20.5 mA Failure Mode: ≤ 3.6 mA and ≥ 21.0 mA
≤ 3.6 mA and ≥ 21.0 mA |
Output Accuracy (HART/DE only) | ±0.005 % span |
Supply Voltage Effect | 0.005 % span per volt. |
Transmitter Turn on Time (includes power up & test algorithms) | HART or DE: 2.5 sec. Foundation Fieldbus: Host dependant |
Analog Input | Stability: 0.01% of URL per Year for 10 years Maximum Lead Wire Resistance: Thermocouples: 50 ohms per leg RTD (all except Pt15) and Ohms: 50 ohms per leg RTD Pt25: 10 ohms per leg |
Response Time (delay + time constant) | DE/HART Analog Output FOUNDATION
Fieldbus Single Input: 130 - 230
mSec
Host Dependant Dual Input: 305 - 455
mSec
Host Dependant |
Update time | 125 mSec for single input units 250 mSec for dual input units |
Damping Time Constant | HART: Adjustable from 0 to 102 seconds in 0.1 increments. Default:
0.50 seconds DE: Discrete values 0.0, 0.3, 0.7, 1.5, 3.1, 6.3, 12.7, 25.5, 51.1,
102.3 seconds. Default: 0.3 seconds |
Ambient Temperature Effect | Digital Accuracy For RTD Inputs: 0.0015 °C/°C For T/C Inputs: 0.005 °C/°C Output D/A: 0.0005 % of span/°C |
Cold Junction Accuracy | ±0.25 °C |
Total Reference Accuracy | Digital Mode Digital Accuracy + C/J Accuracy (T/C input types only) Analog Mode (HART/DE only) Digital Accuracy + Output D/A Accuracy + C/J Accuracy (T/C input
types only) Example: Transmitter in Analog Mode with Pt100 sensor
and 0 to 200°C range Total Reference Accuracy = 0.10°C + (200 °C /
100 %) * 0.005 % = 0.11 °C |
Sensor Burnout | Burnout detection is user selectable. Upscale or down scale with
critical status message. For RTD or ohm type inputs; broken
wire/wires will be indicated |
Digital Output | Contact Rating Voltage: +12 to +30 Vdc. Current: 40mA maximum (controlled by load resistance) Low Level: 0 to 2 Vdc |
Vibration Effect | Per IEC60770-1 field or pipeline, high vibration level (10-2000Hz:
0.21 displacement/3g max acceleration) |
Electromagnetic Compatibility | IEC 61326-3-1 |
Isolation | 2000 Vdc (1400Vrms) Galvanic isolation between inputs and output. |
Stray Rejection | Common Mode AC (50 or 60 Hz): 120 dB (with maximum source impedance of 100 ohms) or ± 1 LSB
(least significant bit) whichever is greater with line voltage
applied. DC: 120 dB (with maximum source impedance of 50 ohms) or a ±1 LSB
whichever is greater with 120 Vdc applied. DC (to 1 KHz): 50 dB (with maximum source of impedance of 50 ohms) or ±1 LSB
whichever is greater with 50 Vac applied. Norma l Mode AC (50 or 60 Hz): 60 dB (with 100% span peak-to-peak maximum) |
EMC Compliance | EN 61326-1 and EN 61326-3-1 (SIL) |
Lightning Protection Option | Leakage Current: 10 uA max @ 42.4 VDC 85 °C Impulse rating: 8/20 uS 5000 A (>10 strikes)
10000 A (1 strike min.)
10/1000 uS 200 A (> 300 strikes) |