Dual Redundant Power Supply Module KJ3001X1-BA1 VE4001S2T1 12P0549X112
|
Dual Redundant Power Supply Module KJ3001X1-BA1 VE4001S2T1
12P0549X112 Nemko No. 02ATEX431U EEx nA IIC T4 b.Power Specifications LocalBus power rating:12 VDC at 100 mA Field circuit rating:24 VDC at 5 mA/channel c.Environmental Specifications Ambient Temperature:0 to 60oC Shock:10g ½ Sinewave for 11 msec Vibration:1mm Peak to Peak from 5 to 16Hz; 0.5g from 16 to 150Hz Airborne Contaminants:ISA-S71.04 –1985 Airborne Contaminants Class G3 Relative Humidity:5 to 95% Non-Condensing IP 20 Rating Terminal block key position:B2 Note: Refer to the product label for serial number and location and date
of manufacture. Refer also to the wiring diagram on the left side
of the card. Warning: This product has specific instructions for installation, removal
and operation in hazardous areas. Refer to document 12P2046
"DeltaV™ Scalable Process System Zone 2 Installation Instructions". Other installation instructions are available in the "Installing
Your DeltaV™ Safety Instrumented System Hardware" manual. Field power supplied to this device, either at the field terminal
or as bussed field power through the carrier, must be removed
before removing or connecting the device. This unit may be removed or inserted while system power is
energized under the following conditions: (Note:Only one unit at a time may be removed or inserted with
system power energized.) •When used with KJ1501X1-BC1 System Dual DC/DC Power Supply
operating on either 24VDC or 12VDC input power, The primary circuit
wiring inductance less than 23 uH, or a certified supply with an
open circuit voltage, Ui of 12.6VDC and an Lo of less than 23 uH
(including wire inductance). •Non sparking field circuits MUST be deenergized before removing
and inserting this product. A terminal block fuse may NOT be removed with field power energized
for non-sparking circuits. A rotary keying system ensures compatibility between I/O cards and
terminal blocks after installation is complete. The terminal block
must have the keys set for the I/O card with which it is used. e.Maintenance and Adjustment This unit contains no user serviceable parts and should not be
disassembled for any reason. Calibration is not required. Other Models:
|
||||||||||||||||||||||||||||||||||||||||||||||||||||
Product Tags: analog interface module diode redundancy module |
![]() |
3BSE000863R0001 SR511 POWER REGULATOR MODULE 310 W MAX 35 AMP 18-30 VDC INPUT 5 VDC OUTPUT |
![]() |
Honeywell TK-FXX102 Redundant Power Supply Module 10SLOT Coated 5.1VDC - 24VDC |
![]() |
Honeywell TC-ODJ161 Output Module Isolated Discrete 16 Point 24 VDC |
![]() |
EMERSON FISHER ROSEMOUNT 01984-1137-0001 POWER SUPPLY I/O PCB BOARD MODULE |
![]() |
AO801 Analog Input Output Module 3BSE020514R1 ABB 20mA 12 Bit RLmax 850 Ohm |
![]() |
ABB AC 800F TK808F Supply Cable 3BDM000211R1 115/230 VAC Euro Plug 2 M |