1000GPM Horizontal Split Case Fire Pump
|
|
1000 GPM Horizontal Split Case Fire Pump Centrifugal Water Pump
UL/FM Fire Pump Performance Requirements:
The maximum net pressure for a fire pump shall not exceed 140 percent of rated head. ( Hs ≤ 140% x H)
Inlet pressure less than 047.7 kpa. A pump shall develop not less than 65 percent or rated total head when discharging at 1-1/2 times rated. (H 1.5 Q ≥ H x 65%)
A test is to be conducted with a positive suction pressure sufficient to achieve the maximum brake-horsepower(KW input)required by the pump. ( P ≥ BHP)
The shut off head shall not be less than 99% of the maximum head.
UL / FM Pump Focus on safety and reliability (short-time running)
1:Working point is different. Fire pump :highest efficiency point is near 1.5Q -- No cavitation, no influence on water absorption performance -- NPSHr curve is not required
2: Matching power is different Fire pump : -- Matching power ensures no overload at any flow rate
3: Hydraulic design is different Fire pump : -- The power curve is required to have an inflection point -- The front end of curve is flat, after 1.5Q, curve fall steep
4: Strength design is different Fire pump :(Shut off head + 50m) x 2
5: Seal form is different Fire pump : Soft packing in principle
Service:
|
||||||
| Product Tags: 1000GPM Horizontal Split Case Fire Pump 180PSI Horizontal Split Case Fire Pump 1000GPM Centrifugal Water Pump |
|
750 GPM @ 155 PSI UL/FM Split Case Fire Pump Electric Motor Driven | NFPA20 |
|
Split Case Fire Pump Up To 249psi For Commercial Buildings In Need Of Fire Protection 3000 GPM |
|
2950 RPM Speed NM6-110B Diesel Engine For Heavy-Duty Applications SCF200-150-250G 1500 GPM |
|
Electric Motor Powered Split Case Fire Pump for Effective Fire Suppression SCF250-200-600 3500 GPM |
|
Automatic Control System and Ductile Cast Iron Heat Exchanger for Industrial Applications SCF300-250-640 4000 GPM |
|
UL Fuel Tank Split Case Fire Pump With High Pressure Rated Pressure Up To 109-179psi And High Flow Rated Flow 7500 GPM SCF400-350-640 |