China Fluid Level Meter manufacturer
Xi'an Kacise Optronics Co.,Ltd.
Kacise, understanding your automation needs.
7
Home > Products > Fluid Level Meter >

10m Ultrasonic Level Sensor 4 - 20mA Automatically Controls Switch Water Level Meter

10m Ultrasonic Level Sensor 4 - 20mA Automatically Controls Switch Water Level Meter

Brand Name KACISE
Model Number KUM-A
Certification CE
Place of Origin CHINA
Minimum Order Quantity 1PCS
Price USD157 to USD610 per pc
Payment Terms T/T, Western Union, MoneyGram
Supply Ability 1000 Piece/Pieces per Week negotiable
Delivery Time 5-8 work days
Packaging Details each unit has individual box and all boxes are packed in standard packages or customers requests available
Product type integrated
Power Supply 24 VDC Optional: 220V AC+15% 50Hz
Display English Led Display
Cable Probe No
Digital Output RS485
Resolution 3mm or 0.1%
Product Name Digital Integrated Ultrasonic Level Meter Non-Contact Level Sensor Level Mesurement Used in Municipal Project
Apply liquid solid
Detailed Product Description

10m Ultrasonic Level Sensor 4 - 20mA Automatically Controls Switch Water Level Meter

Note: Range information is very important

The 10m Ultrasonic Level Sensor is a remarkable device. It features a 4 - 20mA output and can automatically control the switch of the water level meter. With a maximum sensing range of 10 meters, it accurately measures water levels, making it highly suitable for various water level monitoring and control applications.

 

Technical Features:

 

  • Non-contact, can be used in various applications;
  • Various types of probes are available to meet the requirements of various applications.
  • High accuracy: 0.5%, 1%
  • English LED Display

 

Structure:

 

 

Technical Specifications:

 

SpecsValue
Pressure Voltage5m, 10m, 15m, 20m, 30m, 40m, 50m, 60m
Accuracy0.5%, 1.0%
DisplayLCD
Ambient TemperatureDisplay instrument-20~+60℃
transducer-20~+80℃
Mediumliquid and solid
Analog Output4-20mA
Digital OutputRS485, RS232 (both are optional)
Power Supply24Vdc
Protection GradeDisplay instrument IP65,transducer IP68
Probe TypePVDF, aluminum alloy, ABS, stainless steel 316L, teflon, titanium alloy

 

 Model Selection:

 

KUM-A

 

Measurement Range

A

5m

B

10m

C

15m

D

20m

E

30m

F

40m

G

50m

H

60m

 

Output Signal

A

4-20mA

 

Accuracy

0.5

0.5%

1.0

1%

 

Power Supply

A

24Vdc

 

B

11~30Vdc

 

 

Probe Type

A

PVDF

B

Aluminum alloy

C

ABS

D

Stainless steel 316L

E

Teflon

F

Titanium alloy

 

Applications and Installations:

 

  • Distance measurement
  • Depth measurement

 

 

Common problems and solutions guidance during installation

 

Fault description

cause of issue

Solution

Meter does not display, does not work

Wrong power supply Wrong wiring

Check whether the DC24v power supply is correct Check whether the wiring is correct

The instrument has display, does not work

1. The level gauge is not aligned with the liquid level or material level
2. The liquid level fluctuates greatly
3. The material surface is extremely uneven
4. The liquid surface has a thicker foam layer
5. The bottom of the container is not flat after the liquid is emptied and the material is emptied
6. Out of measurement range

1. Adjust the alignment direction of the level gauge, and use a spirit level to calibrate and add a plastic tube to the container 
2. Use a level gauge with a larger range
3. Use a level gauge with a larger range or other measurement methods
4. Naturally resume work after adding liquid or material
5. Use a level gauge with a larger range

The instrument display is unstable or the measured value has a large deviation

1. The material level enters the blind spot
2. The distance measurement value is greater than the installation height
3. There is strong electromagnetic interference
4. Objects that block sound waves
5. A metal flange is prepared on the level meter
6. The emitting surface or side of the probe is in contact with metal

1. Elevate the level meter or prevent the level from being too high
2. Modify the installation height to the correct value
3. The instrument must be connected to the ground, and shield the level gauge
4. Change the installation position or add plastic pipes
5. Switch to plastic flanges
6. Use rubber pads to isolate from metal

 

 

For the container with the installation port or the probe placed in the round pipe, the length of the flange connection of the 4m, 6m and 8m type level gauge container should be less than 400mm, and the length of the 12m level gauge container should be less than 400mm.
150mm, 15m, 20m, 30m level sensor probes should protrude from the installation port.

Product Tags: 10m Ultrasonic Level Sensor   Automatically Controls Switch Ultrasonic Level Sensor   20mA Water Level Meter  
Related Products
Email to this supplier
 
From:
Enter your Email please.
To: Xi'an Kacise Optronics Co.,Ltd.
Subject:
Message:
Characters Remaining: (80/3000)