The DS200TBCBG1AAA is a Termination Analog Card in the GE
Speedtronic Mark V LM series of turbine control systems and can be
mounted within a Mark V turbine control cabinet with other I/O
control boards. There are four sections of these boards within the
cabinet with 9 total slots within an I/O control section.
The TBCB board typically takes up one of the larger slots below a
series of 5 smaller boards. This board is also called a Termination
Module RTD and 4-20 mA Input (TBCB) and functions within the R5
core. Its primary function is to use the input signals that it
receives to transmit them to the TCCB board where they are written
on to the board. It has specific hardware configurations that need
to be setup in the installation process.
The BJ1 to BJ22 input signals need to be connected to the DCOM. The
BJ23 to BJ30 input signals are where signals 15-22 are converted to
0-1mA current range. A total of eight of the regular input signals
have the ability to be converted to 0-1 mA input signals.
The DS200TBCBG1A is a Termination Analog Card in the GE Speedtronic
Mark V LM series of turbine control systems. This board is not
being supported by its original manufacturer anymore and has become
hard to locate at times.
The DS200TBCBG1A can be mounted within a Mark V turbine control
cabinet with other I/O control boards. There are four sections of
these boards within the cabinet. There are 9 total slots within an
I/O control section and the TBCB board typically takes up one of
the larger slots below a series of 5 smaller boards.
The DS200TBCBG1A is also called a Termination Module RTD and 4-20
mA Input (TBCB). This board functions within the <R5> core.
This board uses the input signals that it receives to transmit them
to the TCCB board where they are written on to the board. The TCCB
board is also located within the <R5> core. A total of eight
of the regular input signals have the ability to be converted to
0-1 mA input signals.
The DS200TBCBG1A does not have any specific software that needs to
be configured but it does have hardware configurations. The BJ1 to
BJ22 input signals need to be connected to the DCOM. The BJ23 to
BJ30 input signals are where signals 15-22 are converted to 0-1mA
current range.
Please refer to Instruction Manual GEH-6353B for more information
on the specific installation of the input signals for the
DS200TBCBG1A.