Introduction: - RPT-PC6 Automatic Secondary Injection Relay Test Kit with standard 6 phase voltage and 6 phase current output, voltage
125V/phase, current 30A/phase, 6 phases in parallel can up to 180A.
- With digital Signal Processor Microcomputer, so it can not only test the traditional relays and protectors, but also
can test the modern micro computer relays, specially for
transformer differential protection and transfer equipment testing.
- Classic Windows XP operating interface, 8.4 inch resolution of
800*600 TFT true color display.
- Equipped with ultra-thin industrial keyboard and optical mouse,
complete a variety of operations using keyboard or mouse the same
as ordinary PC.
- The main control board is DSP + FPGA architecture, 16 bit DAC
output, generates high - density sine wave 2000 points each circle
to fundamental wave, which greatly improve the wave quality and the
accuracy of the test instrument.
- Using high-fidelity linear amplifier. Both to ensure the accuracy
of a low current, but also guarantee the stability of the high
current.
- USB directly connect with PC, without any adapter cable, easy to
use.
- Can be connected to a laptop computer (optional). Laptop computers
and industrial machines use the same software, no need to re-learn
the methods of operation.
- With a separate DC auxiliary voltage source, output voltage
110V(1A),220V(0.6A), provides relays or protective devices which
require DC power.
- The software with self calibrating function, which avoid to
calibrate accuracy by adjusting relays after open the case, greatly
improve the stability of the accuracy.
Specifications: 1 | AC current source | | Current range | 6x (0~30A)/phase | Current accuracy | 0.5% | 6 phase parallel current output | 180A | Phase current working value for allowed long time | 10A | Power | 300VA/phase | Max. output power of 6 phases in parallel | 900VA | Max. permitted work time of 6 phases in parallel | 10S | Frequency range | 0~1000Hz; accuracy: 0.001Hz | Harmonic time | 2~20 | 2 | DC current source | | Current range | 20A / phase, | power | 300VA/phase | accuracy | 0.5% | 3 | AC voltage source | | Phase voltage output | 6x( 0~125V)/phase | accuracy | 0.5% | Line voltage output | 0~250V | Phase voltage / Line voltage output power | 70VA / 100VA | Frequency range | 0~1000Hz | Frequency accuracy | 0.001Hz | 4 | DC voltage source | | Phase voltage output range | 0~±150V | accuracy | 0.5% | Line voltage output range | 0~±300V | Phase voltage / Line voltage output power | 90VA / 180VA | 5 | Switch terminal | | Switch input terminals | 8 pairs | Dead contact | 1-20mA, 24V ac | Potential flip | 1-6V DC low level 15-250V DC high level | Switch output terminals | 4 pairs, dead contact, rupturing capacity: 110V/2A, 220V/1A | 6 | Time measurement range | | Range | 1ms-9999s | Accuracy | 1ms | 7 | Dimension & weight | | Dimension | 455 (mm)×530 (mm)×220 (mm) | Weight | 30kg | 8 | Power | AC220V±10%, 50Hz, 15A |
|