INTRODUCTIONBS 476 part 6 specifies a method of test, the result being
expressed as a fire propagation index, that provides a comparative
measure of the contribution to the growth of fire made by an
essentially flat material, composite or assembly. It is primarily
intended for the assessment of the performance of internal wall and
ceiling linings. FEATUREStainless steel support frame andCalcium silicate board combustion chamber. Three kinds of sample holders for different thickness of the specimens. Low reflective black finished mild steel Chimney and Cowl assembly
complete with thermocouple mounting points. Compliant stainless steel gas burner. Two K type mineral insulated thermocouples complete with ceramic
insulators. Two pencil type heaters with 1000w installed in combustion chamber. Control gas instrumentation including electronic gas on/off valve,
flow regulating valve, flow meter and manometer. Intelligent single phase power controller with feedback loop for
accurate control of electric heating elements DAQ record automatically the mV output from the thermocouples of the flue gases throughout
the duration of the test. According to the test time, automatically adjust the output power.
Data Acquisition system: Prompted software interface Data recording and display of cowl temperature against time Data recording and display of ambient temperature against time Display of power value in kW Calibration routine Calculation of output rise and calibration value
Parameters of BS476-6 Flame Propagation Properties Tester: 1 | Dimension | Apparatus: 400mm (W) x 600mm x (H) x 300mm (D) Control module: 400mm (W) x 500mm x (H) x 400mm (D) | 2 | Weight | 46kg | 3 | Power supply | AC 220V, 50/60Hz, 5A | 4 | Ambient temperature | 10 ~ 35 Centigrade | 5 | Gas supply | The gas supply specified in the Standard is Standard test gas G112,
as specified in BS 4947. | 6 | Flow | Gas flow for burner adjustable from 0 to 5 nl/min | 7 | Pressure | 1kPa |
|