China Fogging Cannon manufacturer
Henan Shuangxin Fire Environmental Protection Equipment Manufacturing Co., Ltd.
Henan Shuangxin Fire Environmental Protection Equipment Manufacturing Co., Ltd.
3
Home > Products > HVAC Fire Dampers >

Galvanized Steel Sheet HVAC Fire Dampers Rust Proof Electric Reset

Browse Categories

Henan Shuangxin Fire Environmental Protection Equipment Manufacturing Co., Ltd.

City: zhengzhou

Country/Region:china

Tel:86-199-37744500

Contact Person:
Mr.Alios Lee
View Contact Details

Galvanized Steel Sheet HVAC Fire Dampers Rust Proof Electric Reset

Place of Origin China
Brand Name SX
Certification CE,ISO9001
Minimum Order Quantity 1 Set
Price Negotiation
Packaging Details Standard Export Wooden/Nude packing
Delivery Time To be negotiated
Payment Terms T/T; L/C
Temperature sensor valve static nominal operating temperature 70℃ (valve closes automatically)
Item Fire Damper
Valve body Material 2~3mmQ235-A
Local resistance coefficient Resistance coefficient of ≤ 0.5 at full opening
Rated voltage DC24V±10%
Rated current 0.7A
Detailed Product Description

Fire Damper

* Manual control type
* Normally open, the valve will close after the break-down of fuse when the temperature reaches high degrees , stop the smoke to extend along the air duct.
* It can work as a volume control damper when open to adjust the air volume. The blade is reset by manually.

 

Fire dampers are passive fire protection products used in heating, ventilation, and air conditioning (HVAC) ducts to prevent the spread of fire inside the ductwork through fire-resistance rated walls and floors. Fire/smoke dampers are similar to fire dampers in fire resistance rating, and also prevent the spread of smoke inside the ducts. When a rise in temperature occurs, the fire damper closes, usually activated by a thermal element which melts at temperatures higher than ambient but low enough to indicate the presence of a fire, allowing springs to close the damper blades. Fire dampers can also close following receipt of an electrical signal from a fire alarm system utilising detectors remote from the damper, indicating the sensing of heat or smoke in the building occupied spaces or in the HVAC duct system.

 

Fire damper performance parameter table
Serial numbernameperformance parameters
1Standard flange specificationsValve long side b or diameter D (mm)Flange side width (mm)
D≤28020
280≤D≤630,b≤63025
630<D1250,630<b≤125030
1250<D≤2000,1500<b≤250040
D>2000,2500<b≤400050
2Temperature sensorvalve static nominal operating temperature 70℃ (valve closes automatically)
3MaterialValve body2~3mmQ235-A
Bles2mm708-88 Cold rolled plate
AxshaftGB905-82 Cold pull round steel Ф12
Axft sleeveOil-containing metallurgical powder copper sleeve
4Local resistance coefficientResistance coefficient of ≤ 0.5 at full opening
5Paint treatmentGround floor rust proof primer (second floor), outer fire proof paint (medium ash steel paint)
6Rated voltageDC24V±10%
Rated current0.7A
Micro switchAC380V,3A
Torque10~70Kg.f/cm
Action modeautomatic, electric, manual or 70℃ to close the valve
7Fire control valveReset method (open state)Manual reset
Smoke and fire control valveManual reset
Smoke and fire damperManual reset
Remote control smoke and fire damperRemote control manual reset
Automatic reset fire damperElectric reset
8Air leakageIn the standard state, when the pressure difference on both sides of the valve is 500Pa after the valve is closed, no more than 700mm³/㎡/h

 