General
AMC series programmable intelligent meters, adopting AC sampling
technology, can directly or indirectly measure electric voltage and
current of single-phase or three-phase grid. It can be used for
local display, and connecting industrial control devices to form
measuring control systems. Panel overview
Main parameters
| Function | Description&Value | | Measurement | 3-phase AC kWh, kVarh, I, U, kW, kVar, Hz, cosφ and etc | | Display | LCD display | Communication (Optional) | RS485,Modbus-RTU protocol; | Alarm Output (Optional) | 1 channel passive relay,contact capacity 3A/30VDC,3A/250VAC, Used for high,low,unbalance alarm etc. | DI/DO Switching (Optional) | DI (Digital input): 2-channel or 4-channel dry contact digital
input with built in power supply DO (Digital output): 2-channel digital output with NO relay
contact. Capacity: 3A/30V DC,3A/250V AC | | Input | Rated Voltage | AC Voltage Input: 400V AC L-L (via direct connetion); 100V AC L-L
(via -/100V AC PTs) | | Rated Current | AC Current Input: 5A AC or 1A AC (via -/5A AC or -/1A AC CTs) | | Overload | Current&Voltage input overload:1.2 times rated
value(continuous); 10 times rated value /1 second | | Measuring Accuracy | Active Power | 0.5% | | kWh | 0.5% | | kVarh | 1.0% | | Insulation resistance | ≥ 100MΩ | | Power frequency withstand voltage | Between Power supply//Switching Output// Current Input//voltage
Input and Transmitting// Communication //Pulse Output//switching
input AC 2 kV 1min; Between Power supply,switching output,Current Input,voltage Input
AC 2 kV 1min; Between Transmitting,Communication,Pulse Output,switching input AC
1kV 1 min; |
Dimension
Contact us
|