General
AMC16Z series multi channel din rail ac power meter is
independently designed to meet the needs of the increasingly high
precision power distribution management requirements of the data
center. It is suitable for carious all-round inrelligent monitoring
of terminal distribution equipment. Technical parameter
| Technical parameter | AMC16Z-ZA | | Measured parameter | Voltage, current, frequency, active power, reactive power, power
factor, active power, reactive power | Zero ground voltage, neutral line current, total harmonic content
(THD), 2-63 harmonics, current and voltage unbalance degree, current K coefficient (KF), voltage crest coefficient (CF),telephone waveform factor ( ), peak voltage, voltage and current sequence quantity, environmental temperature and humidity. | | Busbar voltage | Rated | 220VAC | | Measurement | ±20% | | Overload | Instant voltage 2times/second | | Current incoming circuit | Rated | Twice 5A | | Range | 0~6A | | Overload | Duration 1.2 times, instantaneous 10 times/second | | Temp &humidity | Temp range | -40℃~+99℃ | | humidity range | 20%~90% | Input frequency | 45~60Hz | | Measurement precision | Inlet wire | Voltage/current level 0.2, active power/electric energy level 0.5,
reactive power/electric energy level 1 | | Temp | ±1℃ | | Humidity | ±5% | | Auxiliary power supply | Take electric signal(≤15W) | | Environment | Temp | Working:-15℃~55℃ Storage:-25℃~70℃ | | Humidity | Relative humidity ≤93% | | Altitude | ≤2500m | | Switch output | 2-way 3A 250VAC/3A 30VDC | | Switch input | 6-way dry contact | | Communication | RS485/Modbus-RTU | | Installation method | DIN35mm Guide rail or bottom plate mounting |
Features
Wiring
Contact us
|