All In One High Density Optimized Dedicated Modular Data Center
Solution For IT Devices Product Introduction
Micro module data center includes cooling modules, distribution
modules and power supply, as well as modules for network, wiring,
monitoring, and fire fighting. Micro-module data center is designed according to the principles of
high efficiency, energy saving, and optimized management. The micro data center has external power supply interfaces, cooling
interfaces, network interfaces, and The integrated wiring interface
is reserved for the overhead weak and strong current tanks, and the
In Row air conditioning is used for cooling, which achieves a high
sensible heat ratio of 100%, effectively reducing the overall
humidification and dehumidification energy consumption of the data
center, and the In Row air conditioner circulates airflow The road
is the shortest, increasing the heat density of the data center
under the premise of effective cooling, and realizing the
energy-saving cooling of the data center. Benefits
| |
Features
| Hot and cold aisle containment Precision in-row air conditioners are used for near-end cooling,
combined with airflow containment components. The air conditioners
are placed side by side with the cabinets, close to the cabinets,
and directly cool the service cabinets.
Fast deployment Full integration of IT cabinet, UPS, battery, power distribution
and precision cooling system. The main body of the building and the
basic water and electricity construction are completed at one time,
and the micro-modules are flexibly deployed as needed. Modular
components following international standards are quick to play
within 7 days and greatly shorten the business on line cycle.
Modular construction Knocked down components shipped from the factory with an
easy-to-assemble at site design. Part-wise build up from the base with lowest dependency on physical
infrastructure at site.
Safety and Reliability N+1/2N redundant design. The continuous power supply with back up
battary guarantees stable IT equipment operation. Multi-stage automatic alarm function. Real-time system condition
monitoring. Containment top panel can be opened by the fire system. |
Main Basic Unit Introduction
Rack Multi-functional cabinet developed for large, medium and small data
centers. It has the advantages of sturdy structure, strong
load-bearing capacity, noble and elegant and assembling structure
design. Cabinet integrated three major solutions (power management
solution, cable management solution, heat dissipation management
solution), It can be used as a modular equipment installation
infrastructure, cabinet-type power distribution cabinet,
rackmounted battery box, Cabinet integrated user equipment, power
distribution, UPS, battery box, and monitoring system, greatly save
the equipment area in the computer room.
Power Supply- Modular UPS According to the power supply requirements of large and
medium-sized data centers, a modular UPS solution has been
introduced, which can be flexibly configured with 80-300kVA modular
UPS according to the customer's system power supply requirements.
The module adopts advanced high-frequency switching technology,
fully digital DSP control technology and the world’s leading active
PFC and LLC topologies to achieve high input power factor, accurate
output current sharing performance, and reliable monitoring and
management system. The equipment provides safe, reliable and pure
AC power.
End gate (1) The end doors of the aisle are divided into sliding doors and
double doors, which can be selected according to customer needs. (2) Sliding door size: height × width × depth = 2050mm × 1200mm ×
42mm. The sliding door adopts a sliding structure, the cabinet is used as
the carrier, and the upper and lower rails are installed to ensure
the independence of the closed channel system. The door panel is
bent from 1.5mm cold-rolled steel plate, and tempered glass is
installed in the middle to ensure the visibility of the area in the
passage. | |
Air Supply Method
Technical Specification
Equipment System | Item | Parameter | System | Dimension | 1200mm enclosed cold/hot aisle dual-row cabinets | | | 1200mm enclosed cold/hot aisle Single-row cabinets | | Rack Quantity | Dual Row Racks:≤48,Single Row Racks:≤24 | Rack | Dimensions | 600mm(W)*1200mm(D)*2000mm(H), can be customerized,42U | | Protection Class | IP20 | Enclosed Aisle | Skylight | 300mm / 600mm wide turning skylight,Flat roof skylight,Fixed
skylight | Power Supply and Distribution | Dimension | 600mm(W)*1200mm(D)*2000mm(H) | | UPS Power Supply | 380VAC/400VAC/415VAC(3Phase 5Wire),50/60Hz,PF=0.99 | | Battery | 40AH~240AH/12V Valve Regulated Lead Acid Battery | Cooling | Indoor Unit Size | 300mm(W)*1200mm(D)*2000mm(H),600mm(W)*1200mm(D)*2000mm(H) | | Cooling Capacity | Cooling:20~40KW,Chilled water :20~70KW,Chilled water :20~70KW | | Power Supply | 3Phase 380VAC,50Hz | | Air Supply | Front Supply | | Type | Enclosed Hot/Cold Aisle | | Protection | IP20 | Monitoring System | Monitoring | Temperature and humidity, smoke detection, smart access control,
camera, water leakage alarm | | Equipment monitoring | Power supply, battery, power distribution, air conditioning |