Bare AAC Aerial Bundled Cable 600V Service Drop Wire
CONSTRUCTION
Aerial Bundled Cable is extensively used in overhead power
transmission line and used in city streets and green area, overhead
lines closing to the building , the urban construction site and
transformer wiring occasion etc.. It improves the safety and
reliance of electrified wire netting.
TECHNICAL PARAMETERS:
(1)Designated sizes are: ACSR 6/1 diameter equivalent and AAC with
equivalent resistivity per ASTM B-399 for 6201.
| Phase conductor | | | | | | | | | | | |
| Nominal cross-sectional area | mm² | 16 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 | 185 |
| Number of cores | | 1 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 |
| Minimum number of wires | | 6 | 6 | 6 | 6 | 6 | 12 | 15 | 15 | 30 | 30 |
| Nominal insulation thickness | mm | 1 | 1 | 1.2 | 1.2 | 1.4 | 1.4 | 1.6 | 1.6 | 1.8 | 2.0 |
| Diameter of insulated core | mm | 6.8 | 6.8 | 8.5 | 9.5 | 11.2 | 13.0 | 15.1 | 16.6 | 18.4 | 20.6 |
| Max. DC resistance at 20℃ | ohm/km | 1.91 | 1.91 | 1.20 | 0.868 | 0.641 | 0.443 | 0.320 | 0.253 | 0.206 | 0.164 |
| Current rating at still wind, ambient | A | 61 | 61 | 84 | 104 | 129 | 167 | 209 | 246 | 283 | 332 |
| temperature=30℃ |
| Conductor temperature=75℃ | | | | | | | | | | | |
| Messenger conductor | | | | | | | | | | | |
| Nominal cross-sectional area | mm² | 25 | 25 | 25 | 25 | 35 | 50 | 70 | 70 | 95 | 120 |
| Minimum number of wires | | 6 | 6 | 6 | 6 | 6 | 6 | 12 | 12 | 15 | 15 |
| Nominal insulation thickness | mm | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.4 | 1.4 | 1.4 | 1.6 | 1.6 |
| Diameter of insulated core | mm | 8.5 | 8.5 | 8.5 | 8.5 | 9.5 | 11.2 | 13.1 | 13.1 | 15.1 | 16.6 |
| Max. DC resistance at 20℃ | ohm/km | 1.312 | 1.312 | 1.312 | 1.312 | 0.943 | 0.693 | 0.469 | 0.469 | 0.349 | 0.273 |
| Calculated breaking load | kN | 6.4 | 6.4 | 6.4 | 6.4 | 8.9 | 12.1 | 18.0 | 18.0 | 24.2 | 30.8 |
| Completed cable | | | | | | | | | | | |
| Approx. overall diameter | mm | 15.3 | 19.0 | 23.2 | 25.6 | 30.0 | 34.9 | 40.6 | 44.1 | 49.2 | 54.9 |
| Approx. weight of cable | kg/km | 160 | 290 | 400 | 500 | 680 | 920 | 1270 | 1510 | 1870 | 2340 |
| Packing length | m/drum | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 500 | 500 | 500 | 500 |
PACKING AND SHIPPING
We are capable of meeting the most strict delivery schedules
according to per purchase order. Meeting the deadline is always the
top priority as any delay in the delivery of cable can contribute
to overall project delay and cost overrun.
Cable Drum Data
| CABLE DRUMS | D1=Flange Diameter(mm) | W=Useful Width (mm) | D2=Barrel Diameter(mm) |
| 1000 | 700 | 500 |
| 1100 | 700 | 550 |
| 1200 | 700 | 600 |
| 1400 | 750 | 710 |
| 1600 | 900 | 900 |
| 1800 | 1120 | 1000 |
| 2400 | 1150 | 1300 |