Bare AAC All Aluminium Conductor For Distribution Lines

Brand Name Sanwu
Model Number AAC-005
Certification ISO CCC
Place of Origin Henan
Minimum Order Quantity 1000M
Price Negotiable
Payment Terms L/C, T/T, Western Union, MoneyGram
Supply Ability 200 tons per day
Delivery Time 1-15days
Packaging Details New wooden drum, Reel, Circle or according to customer's request
Name AAC All Aluminium Conductor
Type Bare
Application Distribution Lines
Standard ASTM,BS,DIN,AS/NZS,IEC, CSA
Port Qingdao
Packing Wooden drum
MOQ 10KM
Sample Free
Cross Section area: 10-800mm2
Type of Conductor: Stranded
Detailed Product Description

Bare AAC All Aluminium Conductor For Distribution Lines

 

Application of AAC All Aluminium Conductor

 

AAC All Aluminium Conductor has been widely used in power transmission lines with various voltage levels, because they have such good characteristics as simple structure, convenient installation and maintenance, low cost large transmission capacity. And they are also suitable for laying across rivers valleys and places where special geographical features exist.

 

AAC All Aluminium Conductor Service Performance

(1).The permissible long-time operating temperature for aerial conductor is 70oC.

(2).Under the circumstance that rare climate occurs and high ice coverage rate, the biggest stress of cable at the lowest point of the sag should not exceed 60% of the short-time destructive power.

(3).When connecting conductors, the conductor beside the connecting tube can’t be prominent. Otherwise, the force on the operating conductors will be unbalanced. After connectors are installed, the connecting tube should be painted by moisture-proof varnish in order to protect it from corrosion.

(4).Under installation, the arc downing stress of all the conductors should be the same. With in the permissible distance of crossing buildings or dropping to the ground, the stress can be 10-15% higher than regular stress.

 

Nominal

area

Stranding &wire diameter

Approx Overall diameter

Breaking Load

DC Resistance at 20

Approx.

Weight

mm

mm

N

Ω/km

Kg/km

16

7/1.70

5.10

2840

1.802

43.5

25

7/2.15

6.45

4355

1.127

69.6

35

7/2.50

7.50

5760

0.8332

94.1

50

7/3.00

9.00

7930

0.5786

135..5

70

7/3.60

10.80

10950

0.4018

195.1

95

7/4.16

12.48

14450

0.3009

260.5

120

19/2.85

14.25

19420

0.2373

333.5

150

19/3.15

15.75

23310

0.1943

407.4

185

19/3.50

17.5

28440

0.1574

503.0

210

19/3.75

18.75

32260

0.1371

577.4

240

19/4.00

20.00

36260

0.1205

656.9

300

37/3.20

22.40

46850

0.09689

820.4

400

37/3.70

25.90

61150

0.07247

1097

500

37/4.16

29.12

76370

0.05733

1387

630

61/3.63

32.67

91940

0.04577

1744

800

61/4.10

36.90

115900

0.03588

2225

 

Product Tags: Bare AAC All Aluminium Conductor   Distribution Lines AAC All Aluminium Conductor   Distribution Lines AAC Conductor  