Remote Monitoring 48VDC RS485 Module Rectifier Module Telecom
|
|
48VDC Telecom Power Supply Rectifier 120A 6400W Four 30A Rectifier Module Hot Pluggable Ethernet RS485
Model: GPE48120E
Introduction
Embedded DC Power provides stable -48V DC power for wireless and fixed access networks, transmission networks and enterprise network equipment. It consists of a power distribution unit, rectifiers, and a controller, etc., and can be deployed independently or embedded into other power cabinets.
GPE48120E System Configuration
GPE48120E consists of power distribution unit, rectifier module (from 1 set, up to 5 sets) and 1 monitoring module. The configuration is optional, as following table:
GPE48120E Operating PrincipleAC power is first input AC-INPUT MCB and then feed into the rectifier module after lightning proof and filtering. AC-INPUT acts as protection to over load and short circuit to AC power. The user’s battery is connected to the DC output side through battery MCB and KM2, and the circuit breaker provides disconnection control, over-load and short-circuit protection to the battery. Under normal conditions, every parameter of rectifier modules and power distribution unit are all under control of the monitoring module, operating according to the pre-set parameter or user’s commands. If AC mains faults, the battery will power to the system. With the battery discharge, the terminal voltage of the battery starts to descend. When battery voltage is under -47V±0.5V, the monitoring module sends DC under voltage alarm signal and when battery voltage is under -46.0V±0.5V (adjustable), the KM1cuts off non-priority loads and retains power to priority loads. If battery voltage drops to -43.0V±0.5V (adjustable), the KM2 will cut off output of priority loads and then the power system will stop working. If the external AC mains recovers, the system will normally work again. (All above monitoring data are system default values and can be reset by user).
System Specifications
Mechanical Specifications
Electrical Connection
Chassis connects with external electric through system interface board. As shown in figure below:
Power Distribution Instruction:
GPE48120E Distribution Frame
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Product Tags: RS485 Module Rectifier Module Telecom 48VDC Rectifier Module Telecom 48VDC rectifier used in telecommunication | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
DC48V Rack Mount Rectifier 90A High Capacity 220VAC Telecom Single Phase Rectifier |
|
18kW Capacity Rectifier Power System With Power Distribution And Battery Monitor Function |
|
220VAC Rectifier System Up To 3.48kW With RS485 For Telecom Applications |
|
ETP4890 Telecom Rectifier |
|
4800W Rectifier System For Telecom |
|
19inch 220VAC Telecom Rectifier With Monitoring Module |