SHSL-D4 Series Heat Exchanger Radiator For Power Station
Features
Air discharge direction | |
Performance ranges | Cooling capacity: from 5 to 649 kw Air volume: from 2828 to 263503 m3/h Sound pressure level: from 31 to 69 dB A(10m) Dry coolers:customized on demand |
High efficiency heat exchanger | Capacity designs for maximizing the heat transfer relative to the
energy consumption of the fan. Tube and tube coupling design for low pressure drop in the coil on
the media sides(maximum 100KPa at water designing condition). Our thermodynamic and aerodynamic designing software is long year
tested and proved in Germany |
Fan | Only choose low specific energy consumption fans. Fan nozzle designs for maximum air flow and air throw. Our fans from the world`s leading manufacturer are practically
proved to be reliable in operation and long lasting. Motor: protection class IP 54 and insulation class F. Voltage:400V/3N/50Hz Air separator for each fan. |
Testing | Heat exchangers are supplied clean and tested at a pressure of 30
bars |
Options | Coil design refrigerant: water, oil, glycol. Multiple circuits. Sub-cooling circuits. Stainless steel or aluminum casing. Coated aluminum or copper fins. Explosion ploof motor. Customized fin spacing. |
Technical parameter
Dry cooler D4 series parameter(fin space 2.1mm)
Type | D4-428- 10X800 | D4-488- 10X800 | D4-510- 10X800 | D4-520- 12X800 | D4-591- 12X800 | D4-617- 12X800 | D4-724- 14X800 | D4-792- 16X800 |
Capacity | Water | 35℃ outdoor temp. | Inlet | 45℃, | KW | 427.6 | 488.1 | 509.9 | 519.9 | 590.7 | 616.7 | 723.6 | 791.6 |
outlet | 40℃ |
20% Glycol | Inlet | 45℃ | 411 | 476.6 | 498.6 | 503.5 | 579.2 | 605.5 | 712.4 | 777.2 |
outlet | 40℃ |
Medium | Water flow | M3/h | 74.3 | 84.9 | 88.7 | 90.4 | 102.7 | 107.2 | 125.8 | 137.6 |
Pressure drop | kPa | 28 | 60 | 48 | 43 | 99 | 78 | 99 | 99 |
Air flow | M3/h | 216938 | 202183 | 193538 | 260320 | 242613 | 232238 | 270940 | 323168 |
Fan motor(400V/3N/50HZ) | W | 18000 | 18000 | 18000 | 21600 | 21600 | 21600 | 25200 | 28800 |
A | 38 | 38 | 38 | 45.6 | 45.6 | 45.6 | 53.2 | 60.8 |
Fan | No X φ | 2X5X800 | 2X5X800 | 2X5X800 | 2X6X800 | 2X6X800 | 2X6X800 | 2X7X800 | 2X8X800 |
Sound pressure level | dB(A) | 60 | 60 | 60 | 62 | 62 | 62 | 64 | 66 |
10m |
Dimension | L | mm | 6270 | 6270 | 6270 | 7470 | 7470 | 7470 | 8670 | 9870 |
W | mm | 2520 | 2520 | 2520 | 2520 | 2520 | 2520 | 2520 | 2520 |
H | mm | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 | 2000 |
Inlet φ | mm | 2X4” | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 |
Inlet φ | mm | 2X4” | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 | 2XDN125 |
Product weight(empty) | kg | 2159 | 2250 | 2327 | 2480 | 2568 | 2741 | 2947 | 3342 |
Application of radiator in cooling diesel generator set:
Cooling method: The water in the dry cooler system uses a heat
exchanger to cool the circulating water or oil inside the
generator.
Reference:
For power plant | Country: Hongkong Application: power plant Cooling capacity: 363kW Cooling medium: water Supply power: 415V/3P/50Hz Fan brand: Chinese brand | Country: Russia Application: power plant. Cooling capacity: 180kW Cooling medium: water Supply power: 380V/3P/50Hz Fan brand: Chinese brand | |
| | | |