: High-quality pressure transmitter for general industrial
applications; model S-20; see data sheet PE 81.61 Pressure sensor
with IO-Link; model A-1200; see data sheet PE 81.90 WIKA data sheet
PE 81.60 ∙ 05/2023 Pressure transmitter For general industrial
applications Model A-10 Description The field-proven model A-10
pressure transmitter (pressure sensor) is the all-rounder for
pressure measurement in industrial environments. Compactly built,
it can be integrated into a wide range of machine designs. The many
measuring ranges, and special measuring ranges, contribute to its
universal applicability. Excellent quality and proven technology
Our many years of experience and precise knowledge of customer
needs have been incorporated into the development of the model
A-10. It has been proving itself in countless applications for over
ten years. The consistently high quality and its reliable function
are appreciated worldwide and regularly confirmed by both internal
and external audits. This bestseller can tolerate up to 100 million
load cycles with almost constant precision. Exceptionally large
variety covers almost all applications Depending on the
requirement, the model A-10 measures Applications ■ Machine
building ■ Measurement and control technology ■ Hydraulics and
pneumatics ■ Pumps and compressors ■ Shipbuilding
Specifications Optionally the model A-10 is available with an
improved non-linearity. Depending on the selected non-linearity the
following values result: Accuracy specifications Non-linearity ≤
±0.5 % of span Non-linearity ≤ ±0.25 % of span Non-linearity per
BFSL per IEC 61298-2 Measuring range ≤ 0.1 bar [≤ 1.45 psi] ≤ ±0.5
% of span - Measuring range > 0.1 bar [> 1.45 psi] ≤ ±0.5 %
of span ≤ ±0.25 % of span 1) Accuracy → See “Max. measured error
per IEC 61298-2” Max. measured error per IEC 61298-2 Measuring
range ≥ 0.6 bar [≥ 8.7 psi] ≤ ±1 % of span ≤ ±0.5 % of span
Measuring range ≥ 0.4 bar [≥ 5.8 psi] ≤ ±1.2 % of span ≤ ±0.7 % of
span Measuring range ≥ 0.25 bar [≥ 3.6 psi] ≤ ±1.3 % of span ≤ ±0.8
% of span Measuring range ≥ 0.16 bar [≥ 2.3 psi] ≤ ±1.5 % of span ≤
±1 % of span Measuring range ≥ 0.1 bar [≥ 1.45 psi] ≤ ±1.8 % of
span - Measuring range ≥ 0.05 bar [≥ 0.73 psi] ≤ ±2.4 % of span -
Zero point error 2) 3) 4 ... 20 mA / DC 1 ... 5 V / DC 0.5 ... 4.5
V / DC 0.5 ... 4.5 V ratiometric ≤ ±0.3 % of span ≤ ±0.2 % of span
DC 0 ... 10 V ≤ ±0.5 % of span ≤ ±0.4 % of span DC 0 ... 5 V 4) ≤
±0.6 % of span - 1) Not possible with output signal DC 0 ... 5 V.
2) Measuring ranges ≤ 0.1 bar [≤ 1.45 psi] (or equivalent) only
possible with ≤ ±0.5 % of span. 3) Outside reference conditions,
add the temperature hysteresis for measuring ranges < 0.6 bar
[< 8.7 psi]. 4) Not possible with measuring ranges ≤ 0.1 bar [≤
1.45 psi] (or equivalent). In case of occasional faults due to
electrostatic discharges, a temporary additional measured error of
up to ±2.5 % can occur.
Accuracy | ±0.25%F.S |
Output | 4-20mA |
Power supply | 8-32VDC/5VDC |