| Product characteristics |
|---|
| Output function | normally open / normally closed; (selectable) |
| Sensing range [mm] | 20 |
| Housing | cylindrical |
| Dimensions [mm] | Ø 34 / L = 98 |
| Electrical data |
|---|
| Operating voltage [V] | 20...250 AC/DC |
| Protection class | II |
| Reverse polarity protection | no |
| Outputs |
|---|
| Output function | normally open / normally closed; (selectable) |
| Max. voltage drop switching output DC [V] | 6 |
| Max. voltage drop switching output AC [V] | 6.5 |
| Minimum load current [mA] | 5 |
| Max. leakage current [mA] | 2.5 (250 V AC) / 1.3 (110 V AC) / 0.8 (24 V DC) |
| Permanent current rating of switching output AC [mA] | 250; (350 (...50 °C)) |
| Permanent current rating of switching output DC [mA] | 100 |
| Short-time current rating of switching output [mA] | 2200; (20 ms / 0,5 Hz) |
| Switching frequency AC [Hz] | 25 |
| Switching frequency DC [Hz] | 50 |
| Short-circuit proof | no |
| Overload protection | no |
| Detection zone |
|---|
| Sensing range [mm] | 20 |
| Real sensing range Sr [mm] | 20 ± 10 % |
| Operating distance [mm] | 0...16.2 |
| Accuracy / deviations |
|---|
| Correction factor | steel: 1 / stainless steel: 0.7 / brass: 0.4 / aluminium: 0.4 /
copper: 0.3 |
| Hysteresis [% of Sr] | 3...15 |
| Switch point drift [% of Sr] | -10...10 |
| Operating conditions |
|---|
| Ambient temperature [°C] | -25...80 |
| Protection | IP 65 |
| Tests / approvals |
|---|
| EMC | | EN 60947-5-2 | | | EN 55011 | class B |
|
| MTTF [years] | 610 |
| UL approval | | Ta | 0...40 °C | | Enclosure type | Type 1 | | voltage supply | Hazardous voltage | | File number UL | E174191 |
|
| Mechanical data |
|---|
| Weight [g] | 184.5 |
| Housing | cylindrical |
| Mounting | non-flush mountable |
| Dimensions [mm] | Ø 34 / L = 98 |
| Materials | PBT; end cap: PC |
| Displays / operating elements |
|---|
| Display | | switching status | 1 x LED, yellow |
|
| Electrical connection |
|---|
| Required protection | miniature fuse to IEC60127-2 sheet 1; ≤ 2 A; fast acting |
| Accessories |
|---|
| Items supplied | |
| Remarks |
|---|
| Remarks | | Recommendation: Check the safe functioning of the unit after a
short circuit. |
|
| Pack quantity | 1 pcs. |
| Electrical connection |
|---|
| Connection | terminals: ...2.5 mm²; Cable sheath: Ø 7...13 mm; Cable gland: M20
X 1.5 |