MSXP-W10-PA Differential Pressure Transmitter With Monitors
|
Dwyer MSX Pro Differential Pressure Transmitter with Monitors Differential Pressure Series MSX/AT2MS/MS2/DMSERIES MSX PRO MAGNESENSE® DIFFERENTIAL PRESSURE TRANSMITTERMonitors Differential Pressure, Air Velocity and Volumetric FlowThe Series MSX Pro Magnesense® Differential Pressure Transmitter is the professional differential pressure transmitter meeting stringent industry standards with innovative global product design. The device has exceptional stability for use in critical building performance applications with the popular versatility of our original Series MS2 Magnesense® II transmitter. The MSX Pro simplifies the ordering process to deliver the desired configuration, which reduces product setup time. Pressure ranges of Pa, mm w.c., and in w.c. are available per device. All pressure ranges can be configured in unidirectional or bidirectional modes providing a total of 32 ranges. The MSX Pro transmitter can provide a linear pressure output or a linear velocity output with the square root extraction from the transmitter. Additional parameters have been included to expand the square root capability to calculate flow. Dual voltage and milliamp output signals can be used to provide control and equipment output signal verification. NIST CALIBRATION available in Product Configurator. PRODUCT APPLICATIONS
SpecificationsService: Air and non-combustible, compatible gases. Wetted Materials: Consult factory. Accuracy: ±.5% FSO for all ranges except unidirectional .5 in. @ ±1% FSO. Stability: ±1% FSO/year. Temperature Limits: -4 to 158°F (-20 to 70°C). Pressure Limits: Ranges 0 and 1: 3.6 psi max operation, 6 psi burst; Ranges 2, 3 and 4: 6 psi max operation, 6 psi burst. Power Requirements: 10-36 VDC (2-wire), 17-36 VDC or isolated 21.6-33 VAC (3-wire). Output Signals: Output Signals: 4-20 mA (2-wire); 0-10 V or 0-5 V selectable (3-wire). Response Time: Instantaneous (default) or 3 s (selectable). Zero and Span Adjustments: Digital push-button. Loop Resistance: Current output: 0-1250 Ω max; Voltage output: min. load resistance 1 k Ω. Current Consumption: 21 mA max continuous. Electrical Connections: 4-wire removable European style terminal block for 16 to 26 AWG. Electrical Entry: 1/2" NPS thread. Cable gland included. Display (optional): 4 digit LCD. Process Connections: 1/8", 3/16", 1/4", 5 mm, and 6 mm ID flexible tubing. Enclosure Rating: NEMA 4X (IP66), UL 2043 (Plenum), UL94 V-0. Mounting Orientation: Pressure sensor measurement unaffected by orientation. Weight: 8.0 oz (230 g). Agency Approvals: CE.
Features
Model ChartMSXP-XXX-X-OPT MSX PRO DIFFERENTIAL PRESSURE XMTR 1ST SYMBOL (1ST
X) MOUNTING W WALL MOUNT U UNIVERSAL (WALL OR DUCT) N DIN MOUNT 2ND
SYMBOL (2ND X) DIRECTION 1 UNI-DIRECTIONAL 2 BI-DIRECTIONAL 3RD
SYMBOL (3RD X) PRESSURE RANGE 0 0.5 INWC, 125 PA, 12 MMWC 1 1 INWC,
250 PA, 25 MMWC 2 5 INWC, 1250 PA, 125MMWC 3 28 INWC, 7000 PA, 700
MMWC 4TH SYMBOL (4TH X) UNITS OF MEASURE IN INCHES OF WATER COLUMN
PA PASCAL MM MILLIMETERS OF WATER COLUMN OPT (OPTIONS) ADD ON
OPTIONS -A481 STATIC TIPS AND TUBING KIT -FC FACTORY CALIBRATION
CERTIFICATE -FP FILTERED PICKUP WITH BARB -LCD LIQUID CRYSTAL
DISPLAY -NIST NIST CALIBRATION CERTIFICATE -STA STATIC TIPS -WO LCD
COVER WITHOUT LCD DISPLAY
|
||||||||||||||||
Product Tags: Differential Pressure Transmitter MSXP-W10-PA Differential Digital Pressure Gauge Differential Pressure Level Transmitter |
![]() |
Honda HUS-3 Multi-sound Manometer/sound Manometer Ultrasonic Pressure Sensor Portable |
![]() |
KYORITSU AC/DC Clamp Meter KEW2007R Multimeter in Stock |
![]() |
DM-2012-LCD Digital Pressure Gauge Accuracy 1% FS At 70 Fahrenheit Degree |
![]() |
100% Original Brand New Honeywell Temperature Transmitter STT850 STT750 STT650 STT700-1D-10-00000-60A0-11S-A-F1-00000 |
![]() |
Honeywell Universal Transmitter XNX-AMAE-NNNNN H2S Toxic Gas Detector |
![]() |
Honeywell 943 Series Ultrasonic Distance Sensors 943-T4Y-2D-1D0-200EEX Ultrasonic Proximity Sensor |