China Aluminum Housed Wirewound Resistors manufacturer
SHENZHEN JINGDACHENG ELECTRONICS CO.,LTD
All for protecting your circuits, all for electric safety!
5
Home > Products > Resistive Load Bank >

500KW 600VAC Resistive Load Bank 3 Phase For Generator Sets Testing And Maintenance

500KW 600VAC Resistive Load Bank 3 Phase For Generator Sets Testing And Maintenance

Brand Name JDC
Model Number LB
Place of Origin CHINA
Minimum Order Quantity 1
Price US$1,000.00-US$10,000.00
Payment Terms T/T, Western Union
Supply Ability 100 Sets per Month
Delivery Time 3 Weeks
Packaging Details Wooden case
Rated Power 10KW-1MW
Resistance 0.1R-1KR
IP Grade IP23-IP54
Detailed Product Description

500KW 600VAC 3 phase Load Bank for generator sets testing and maintenance

This is an outdoor use pure resistive load bank. It can test both 3 phase 600V at full capacity 500KW. Also can derate use for lower voltages, such as 3 phase 480V, 240V, etc, ans single phase voltages.

 

Working Environment:

Ambient Temperature :-20℃ to +45℃
Relative Humidity:monthly less than 90%, daily less than 95%(25℃)
Altitude:≤1000m
Service Location:indoor/outdoor, not in rain, vertically installed, the inclined degree less than 5 degrees

 

Technical Data:

 

No.ItemDescription
1ModelLB-500kW-AC600V-J
2TypeResistive load bank
3Rated CapacityAC600V(3 phase)-500kW
4Testing Voltage3 phase, AC600V 60 Hz
5LoadingPower continuously adjustable, full capacity can be realized
6Control MethodLocal panel manual control
7Step Resolution5kW
8Power Steps(KW)5KW, 5kW, 10kW, 10kW, 20kW, 50kW, 100kW, 100kW, 200kW
9Delay Control FunctionWhen the input power is cut off, the fan would still work for some time for heat dissipation and automatically stops.
10Brand Of Control Switch DevicesABB, Siemens or Schneider
11Insulation Resistor≥5MΩ (1000V)
12Insulation & Withstand VoltageResistor to Enclosure (2000VAC), leakage current <20mA
13Noise≤90dB (1 meter away from the load bank)
14Enclosure ColorRAL7035 or specified by customer
15Cable Inlet/OutletAt bottom, with rubber plug protection
16Nameplate, Wire No.legible signs and words
17Resistance Accuracy≤±3%
18Reliabilitythe structure of the control part has necessary measures to reduce the impact of vibration and electromagnetic interference such as switch on and off, and ensure the reliable operation of the instruments, relays and monitoring devices
19Control Parameters

1.Display basic functions such as voltage, current, active power, power factor, frequency, etc;

2. Monitor the temperature rise at the air outlets

20Dimension1800mm*1300mm*2200mm (W*D*H)
21Working Methodcontinuous
22Cooling MethodForced Air Cooling(air out from top)
23Measurement AccuracyGrade 0.5
24Auxiliary PowerAC380V/60HZ (3 phase)
25Weight≤ 500kg
Product Tags: 600VAC Resistive Load Bank   500KW Resistive Load Bank   Generator Sets 3 Phase Resistive Load Bank  