The M30 is a compactsite monitoring module that captures module
voltage, current, and alarm information, and adjusts module current
limit, overvoltage point, and control module power on/off. M30
provides RS485 communication interface (1 way north, 2 way south),
rectifier module communication interface (support RS485 and CAN),
sensor interface (ambient temperature and humidity, battery
temperature), 6 input dry contact interface (can Associated access
control, flooding, smoke, lightning protection, oil machine,
temperature control failure, battery out of position and standby
DI), 1 channel three-phase AC detection port, 6 output dry contact
interface, 9 channel current detection, 2 channel battery melting
Wire and 1 total load fuse detection, 5 levels power-down
management, 9-channel user power record, battery management, system
energy saving, etc., to meet the user's demand for power monitoring
functions. The M30 supports the sound and light alarm, the access
of the smart device, the dry contact upload, the RS485 upload, and
the TCP/IP upload mode. The environment information and alarm
information will be reported. SpecificationTechnical | DC Input | Voltage (V) | 40~60Vdc | | Current(A) | ≤0.5A | | Power(W) | Less than 20W | Communication Interface | Rs485 | Default (Modbus Protocol RTU) | | TCP/IP | Default | | SNMP | Customized | | 6 Dry Contact | AC Power Failure,AC Input Fault ,DC Output Fault ,Battery Over
Voltage,DI Dry contact,Rectifier module output Over
Voltage,Rectifier module output Under Voltage,Rectifier Module
Fault,Rectifier Module Communication Fault,Rectifier Module Current
Limiting,Rectifier module current non-equalize,Rectifier module
Protection,Battery Power off ,Load Fuse,Battery Fuse,Battery
Connect Fail | | Signal Input | 1* Battery Temp,1*Ambient Temp,1*Air Conditioning ,. 1*Smoke
Alarm.,1*Flooding Alarm.,1*Access Alarm.,1*Surge arrest,1*
Fan,1*generator | | Baud Rate | 9600 Bit/s | Storage Capacity | Historical Alarm Records | Up to 1000 Units | Display Mode | | LC |
|