TECHNICAL SPECIFICATION |
Model | Smartpack S – Panel Mount |
Part number | 242100.415 |
INPUT DATA |
|
|
Voltage (nominal) | 10 - 75 VDC |
System output grounding | Supports positive, floating and negative distributions. All inputs
are referenced to shunt. |
Power Consumption, max - no relays energized max - all relays
energized | 3,1W (display sleep) 5,5W (display on) |
SYSTEM CONNECTIONS - SYSTEM MONITORS |
|
Voltage sense, system voltage support | 12 VDC, 24VDC, 48VDC & 60VDC |
Current sense, shunt support | 0 - 20mV and 0 - 60mV |
Battery fuse monitoring | Auxiliary switch NO/ NC, Pull up/down |
Load fuse monitoring | Auxiliary switch NO/ NC, Diode Matrix Pull up/ down |
Ground fault detection | Simple bridge circuit detection [Tolerance: ±10%, alarm range: 25
kΩ – 500k Ω] |
Fan speed monitoring | Tacho sense 0 -65000 rpm [Input max. 15V] |
SYSTEM CONNECTIONS - LVD CONTROL |
|
|
Battery disconnect | 1 (latched or non -latched supported) |
Load disconnect | 1 (latched or non -latched supported) |
INPUTS AND OUTPUTS |
|
|
Digital configurations, Inputs #1 -6 | Auxiliary switch: NO/ NC Temperature (for NTC probe) |
Analog configurations, Inputs #1 -4 | Analog Voltage[±0 - 10V] ±4-20mA current measurement (through external 470k Ω resistor) |
Analog configurations, Inputs #5 -6 | Analog Voltage[0 -75V] Symmetry measurement |
Output configurations, Outputs #1 -6 (alarms) | 6x Relay–Dry/ Form C Configurable Normally Open/ Closed [Max capacity 75V/2A/ 60W] |
Fan Control | Analog Voltage [ 0 - 10V] Output Current 0 - 20 mA Fan Input Impedance minimum 10 k Ω |
CAN Power Available for Eltek CAN Nodes | 500mA |
USER INTERFACE |
|
Local | 2.2” TFT 65k Colour display, QVGA resolution, 4 keys |
Ethernet port | 10/ 100 BASE-T (HP Auto MDI/ MDI-X) IP protocols: HTTP / SSL, SNMP v3, MODBUS TCP and pComm UDP
(PowerSuite) |
Serial port | RS-232 and RS-485 on RJ11 connector Serial protocols: MODBUS RTU, Modem Call-Back/SMS reporting (PSTN
or GSM), COMLI, CSCP and pComm (PowerSuite) |
GENERAL SPECIFICATIONS |
|
Dimensions (WxHxD*) * depth behind panel | 232.2 x 76.2 x 33.0 mm (9.1 x 3 x 1.3 ”) |
Temperature Range | Operating -20 to +65 ˚C (-40 to 149 ˚F) |
DESIGN STANDARDS |
|
Electrical safety | UL 60950 -1-3rd edition, EN 60950 -1-3rd edition |
EMC | ETSI EN 300 386 V.1.4.1 EN 61000-6-1 / -2 / -3 / -4 FCC Part 15 Subpart 109 |
Environment | ETSI EN 300 019: 2-1 (Class 1.2), 2-2 (Class 2.3) & 2-3 (Class
3.2) ROHS compliant |
|