96.5% Telecom Rectifier Module Flatpack2 48v 2000w 241115.105
|
Eltek Rectifier Module Flatpack2 48/2000HE 48V 2000W high efficiency (Part No. 241115.105) Flatpack2 48/2000 HEThe combination of innovative design, efficiency and reliability
makes the Flatpack2 HE stand out.
|
Model | 48V / 2000W HE | 48V / 3000W HE |
Part number | 241115.105 | 241119.105 |
INPUT DATA | ||
Voltage (nominal) | 185 - 275 VAC / 185 - 275 VDC | 176 - 277 VAC |
Voltage (range) | 85 - 300 VAC / 85 - 275 VDC | 85 - 305 VAC |
Frequency | 45 - 66 Hz, 15-18.5 Hz1) / 0 Hz | 45 - 66 Hz |
Current (maximum) @ nominal input, full load | 11.6 ARMS | 19.2 ARMS |
Protection | Fuse in both lines Varistor for transient protection Disconnect above 300 VAC/DC | Fuse in both lines Varistor for transient protection Disconnect above 305 VAC |
OUTPUT DATA | ||
Voltage (default) | 53.5 VDC | |
Voltage (adjustable range) | 43.5 - 57.6 VDC | 43.2 - 582) VDC |
Power (maximum) | 2000 W | 3000 W |
Power @ 85 VAC | 850 W | 1380 W |
Current (maximum) @ nominal input, full load | 41.7 A | 62.5 A |
Ripple, 30MHz bandwidth | < 100 mVpp | < 150 mVpp |
Psophometric noise | < 2 mVRMS | < 2 mVRMS |
Static Voltage regulation | ±0.5% for 10 - 100% load | |
Dynamic Voltage regulation | ±5.0% for 10-90% or 90-10% load variation, regulation time < 50ms | |
Protection | Fuse, Short circuit proof, High temperature protection, Hot plug-in inrush current limiting | |
OTHER SPECIFICATIONS | ||
Efficiency @ nominal input | 96 % | |
Isolation | 4.0 kVDC - input to output, 2.5 kVDC - input to earth, 710 VDC - output to earth | 5.0 kVDC - input to output, 2.5 kVDC - input to earth, 710 VDC - output to earth |
Alarms: Red LED 'on' | Low mains shutdown, High and low temperature shutdown, Rectifier Failure, Overvoltage shutdown on output, Fan failure, Low voltage alarm, CAN bus failure | |
Warnings: Yellow LED 'on' | Rectifier in power derate mode, Remote battery current limit activated, Input voltage out of range, flashing at overvoltage | |
Normal (module running): Green LED 'on' | ||
MTBF (Telcordia SR-332 Issue I method III (a)) | >350 000 (@ Tambient : 25 °C) | >300 000 (@ Tambient : 25 °C) |
Operating temperature | -40 to +75°C (-40 to +167°F)4), humidity 5 - 95% RH non-condensing | |
Temperature de-rating | >55°C (131°F), 1200W @ 75°C (167°F) | >55°C3) (131°F), 2100W @ 75°C (167°F)4) |
Storage temperature | -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing | |
Dimensions[WxHxD] / Weight | 109 x 41.5 x 327mm (4.25 x 1.69 x 13”) / 1.95 kg (4.3 lbs) | |
DESIGN STANDARDS | ||
Electrical safety | EN 62368-1:2020+A11:2020, IEC 62368-1:2018, IEC 60950-1:2005+A2:2013 UL 62368-1:2019 , CSA C22.2 No.62368-1:2019 | |
EMC | EN 61000-6-1:2019, -6-2:2019, -6-3:2007+A1:2011+A2:2012+AC:2012, -6-4:2019, EN 61000-3-2:2019, ETSI EN 300 386 V.2.2.0:2020, Telcordia NEBS GR1089 CORE | |
Marine | DNVGL-CG-0339 | - |
Environment | ETSI EN 300 019: 2-1 (Class 1.2) & 2-2 (Class 2.3) EU 2015/863 (RoHS) & 2012/19/EU (WEEE) Normal operating conditions as per IEC 62040-5-3:2016 clause 4.2. Other operating conditions as per IEC 62040-5-3:2016 clause 4.3, must be advised | |
1) power derating, maximum 1000W @ 230Vac 16 2/3 Hz 2) 57.6V for HW revision ≤ 5 | 3) 3kW: from HW revision 6: shutdown at 95°C with de-rating to ~1000W |
Solutions
As experts in the telecommunications field, we deliver a complete solution for telecom companies both within and outside China. Our site survey is conducted with the utmost precision, using advanced tools and techniques to gather accurate data. Based on this information, we propose a highly professional plan that is customized to the customer's unique requirements. Our technical support team is comprised of industry - leading professionals who can resolve any technical issues efficiently, and our maintenance services are designed to ensure the long - term performance and reliability of the telecommunications systems. We have a network of trusted partners around the world who share our commitment to excellence.
FAQ :
1.Q: How do you monitor and control product quality?
2.Q: What's the minimum order quantity you accept?
3.Q: Can you tell me about your company's background and capabilities?
4.Q: What are the competitive advantages of your company?
5.Q: Is it possible to request samples and get a price breakdown?
![]() |
Flatpack 2 110V 2000W HE Rectifier / Converter 241115.805 |
![]() |
Eltek 48V 4000W Rectifier Module FLATPACK2 48/4000 HE 241119.904 High Capacity Module |
![]() |
Eltek V-Series High Efficiency Rectifiers V0750A1- HE V0500A1-HE |
![]() |
Eltek Compact Flatpack S 48V 1000 SHE Rectifier For Small To Medium Telecom |
![]() |
Eltek 48V 60V Converter FP2 Rectifier Module Flatpack 2 48-60/2000he P/N 241115.705 |
![]() |
Eltek 48V 2000W Rectifier Module FLATPACK2 48/2000 HE 241115.105 |