Honeywell 10310/2/1 Earth Leakage Detector
|
Honeywell 10310/2/1 Earth Leakage Detector
Honeywell 10310/2/1 Earth Leakage Detector.pdf
Product Details:
The 10310/2/1 module is an earth leakage detector (ELD) for 24 Vdc systems. It has a manually operated self-test and earth connection monitor (switch 2 in 'TEST' position). The ELD can be used to monitor: • 24 Vdc, 48 Vdc and/or 60 Vdc systems , or • 110 Vdc systems.
The ELD module connects earth level with –12 Vdc (referenced to the 0 V connection of the 24, 48, 60 and/or 110 Vdc supply). This connection is: • continuous (switch 1 in 'DC' position), or • interrupting at 1 Hz (switch 1 in '1 Hz' position), or • interrupting at 0.25 Hz (switch 1 in '1/4 Hz' position). With switch 1 in the '1 Hz' or '1/4 Hz' position, the green 'MODE' LED on the module front flashes at the selected connection frequency.
Switch 1 is normally used in the 'DC' position.
The '1 Hz' position should only be used to accommodate for solenoids or relays that could stay energized by the negative earth voltage. The '1/4 Hz' position can be used for locating earth faults. Locating earth faults requires a current clamp (e.g. the C37 clamp from Chauvin Arnoux) and a voltmeter (200 mV AC range).
|
||||||||
Product Tags: Honeywell 10310/2/1 Earth Leakage Detector Honeywell Earth Leakage Detector 10310/2/1 Earth Leakage Detector |
![]() |
Honeywell MC-TLPA02 51309204-175 Power Adapter |
![]() |
Honeywell MC-TLPA02 51309204-175 LLMUX SDI SI Power Adapter |
![]() |
Honeywell MC-PLAM02 51304362-150 Low Level Analog Input Multiplexer Processor |
![]() |
51401496-100 Honeywell Dual Node Fan Assembly |
![]() |
51401291-100 Honeywell Low Power LCN Interface |
![]() |
51401288-200 Honeywell HPK2-3 Processor Circuit Board |