Output Signal | Supply Voltage | Output Type |
4~20mA | 12~30VDC | 2/3/4 wire |
0~10/20mA |
3 wire |
0/1~5V |
0/1~10V |
0.5~4.5V | 5VDC |
1. When selecting the product, please ensure that the medium to be
measured is compatible with the contact parts of the product.
2. When placing an order, please note that explosion-proof type
products do not include digital display heads.
3. To ensure reliable operation of the product, it is recommended
that users install lightning protection devices on-site and ensure
that the product and power supply are reliably grounded.
4. The rated working temperature range of the Fluoro rubber O-ring
is -20ºC to 250ºC. When the product's operating temperature is
below -20ºC, it is necessary to choose an EPDM O-ring seal.
5. The default cable length is 1.5m, available in three materials.
If not specified, it will be supplied with polyethylene cable
material. If you require a different cable material, please specify
it in the order.
Order Guide |
BP15X | Analog Pressure Transmitter |
| Code | Outline Construction |
5 | Packard plug | 6 | Sealed Direct Output Cable 1.5 meters |
7 | Mini Hirschmann Connector | 8 | Large Hirschmann Connector |
| Measurement Range | 0kPa ~ 10kPa…5MPa |
(0-X)Kpa or MPa | X: Indicates the Actual Measuring Range |
| Code | Power Supply |
D1 | 24VDC |
D2 | 5VDC |
D3 | Other |
| Code | Output Signal | |
S1 | 4~20mADC | S5 | 0~20mADC |
S2 | 1~5VDC | S6 | 0~10VDC |
S3 | 0~5VDC | S7 | 0.5~4.5VDC |
S4 | 0~10mADC | | |
| Code | Pressure Connection |
J1 | M20×1.5 |
J2 | G1/2 |
J3 | G1/4 |
J4 | 7/16-20UNF |
J5 | Others(¢50.4 Flange) |
| Code | Electrical Connection |
B1 | Hirschmann |
B2 | PG7 |
B3 | Cable Sealed Outlet 1.5 meters |
B4 | Other |
| Code | Pressure Type |
G | Gauge Pressure |
A | Absolute Pressure |
S | Sealed Reference Pressure |