Pepperl+Fuchs KFU8-UFC-1.D Frequency Converter With Trip Values
|
|
Product Details:
Technical data 1. General specifications Signal type: Digital Input 2. Functional safety related parameters Safety Integrity Level (SIL): SIL 2 3. Supply Connection: terminals 23, 24 Rated voltage: 20 ... 90 V DC / 48 ... 253 V AC 50
... 60 Hz Power dissipation/power consumption: ≤ 2 W ; 2.5 VA /
2.2 W ; 3 VA 4. Interface Programming interface: programming socket 5. Input Connection side: field side Connection: Input I: 2-wire sensor: terminals 1+, 3-
three wire sensor: terminals 1+, 2- and 3
input II: terminals 13+, 14- start-up
override; Input I: 2- or 3-wire sensor, sensor acc. to EN
60947-5-6 (NAMUR) or mechanical contact Open circuit voltage/short-circuit
current: 22 V / 40 mA Input resistance: 4.7 kΩ Switching point/switching hysteresis:
logic 1: > 2.5 mA ; logic 0: < 1.9 mA Pulse duration: > 50 µs Input frequency: 0.001 ... 10000 Hz Line fault detection: breakage I ≤ 0.15
mA; short-circuit I > 4 mA Input II: startup override: 1 ... 1000 s, adjustable
in steps of 1 s Active/Passive: I > 4 mA (for min.
100 ms) / I < 1.5 mA Open circuit voltage/short-circuit
current: 18 V / 5 mA 6. Output Connection side: control side Connection: output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
outout III: terminasl 19+, 20-
output IV: terminals 8+, 7- Output I, II: signal, relay Contact loading: 250 V AC / 2 A / cos φ
≥ 0.7 ; 40 V DC / 2 A Mechanical life: 5 x 107 switching
cycles Energized/De-energized delay: approx. 20
ms / approx. 20 ms Output III: electronic output, passive Contact loading: 40 V DC Signal level: 1-signal: (L+) -2.5 V (50
mA, short-circuit/overload proof) 0-signal: blocked output (off-state
current ≤ 10 µA) Output IV: analog Current range: 0 ... 20 mA or 4 ... 20
mA Open loop voltage: max. 24 V DC Load: max. 650 Ω Fault signal: downscale I ≤ 3.6 mA ,
upscale ≥ 21.5 mA (acc. NAMUR NE43) 7. Indicators/settings Display elements: LEDs , display Control elements: Control panel Configuration: via operating buttons
via PACTware Labeling: space for labeling at the front 8. Conformity Electromagnetic compatibility: NE 21:2006 Degree of protection: IEC 60529:2001 9. Ambient conditions Ambient temperature: -20 ... 60 °C (-4 ... 140 °F) 10. Mechanical specifications Degree of protection: IP20 Connection: screw terminals Mass: 300 g Dimensions: 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch)
(W x H x D) , housing type C2 Height: 119 mm Width: 40 mm Depth: 115 mm Mounting: on 35 mm DIN mounting rail acc. to EN
60715:2001
Related Models:
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Product Tags: Pepperl+Fuchs kfu8 ufc 1 d kfu8 ufc 1 d Frequency Converter pepperl fuchs kfu8 ufc 1 d |
|
Pepperl+Fuchs NBB20-U4-UU high-performance inductive proximity sensor |
|
Pepperl Fuchs NJ2-11-N-G High-Precision Inductive Proximity Sensor |
|
Wenglor P1KY001High-Precision Time-of-Flight Laser Distance Sensor |
|
Pepperl Fuchs PSM58N-F3AAGROBN-1213 Multi-Turn Absolute Encoder |
|
Pepperl Fuchs KCD0-SD3-EX1.1045 Reliable Safety Relay for Hazardous Area Protection |
|
Pepperl+Fuchs UCC1000-30GM-IUR2-V15 Ultrasonic Sensor |