General specifications |
---|
Switching function | Normally closed (NC) |
Output type | NAMUR, bistable |
Inside diameter | 15 mm |
Measuring cylinder | Fe-metal |
| Diameter | 3 mm |
| Length | 4 mm |
Passage speed | ≤ 10 m/s |
Output type | 2-wire |
Nominal ratings |
---|
Nominal voltage | 8.2 V (Ri approx. 1 kΩ) |
Operating voltage | 5 ... 25 V |
Hysteresis | typ. 1 % |
Reverse polarity protection | reverse polarity protected |
Current consumption | |
| Traverse B | 3 mA |
| Traverse A | 1 mA |
Time delay before availability | ≤ 5 ms |
Functional safety related parameters |
---|
MTTFd | 2240 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Compliance with standards and directives |
---|
Standard conformity | |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Standards | EN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012 |
Approvals and certificates |
---|
ATEX approval | |
| Equipment protection level Gb | PTB 99 ATEX 2128 X |
FM approval | |
| Control drawing | 116-0165 |
UL approval | cULus Listed, General Purpose |
Ambient conditions |
---|
Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) |
Storage temperature | -40 ... 100 °C (-40 ... 212 °F) |
Mechanical specifications |
---|
Connection type | cable PVC , 2 m |
Core cross section | 0.14 mm2 |
Housing material | PBT |
Degree of protection | IP67 |
Cable | |
| Bending radius | > 10 x cable diameter |
Dimensions | |
| Height | 32.5 mm |
| Width | 25 mm |
| Length | 20 mm |
General information |
---|
Use in the hazardous area | see instruction manuals |