Model |
product brand name | SENTRON |
product designation | Motorized operating mechanism |
design of the product | Accessories for VL1250; VL1600 |
type of the driving mechanism | motorized operating mechanism |
General technical data |
operating frequency maximum | 30 1/h |
Voltage |
fuse protection type for external auxiliary power supply required | NEOZED fuse (gL/gG): 2 A / miniature circuit breaker, C char.: 2 A |
operating range factor control supply voltage rated value | |
● at DC initial value | 0.85 |
● at DC full-scale value | 1.1 |
● at AC at 50 Hz initial value | 0.85 |
● at AC at 50 Hz full-scale value | 1.1 |
● at AC at 60 Hz initial value | 0.85 |
● at AC at 60 Hz full-scale value | 1.1 |
Protection class |
protection class IP | IP30 |
Control current |
operating apparent power | 250 VA |
control supply voltage | |
● at DC rated value minimum | 250 V |
● at DC rated value maximum | 220 V |
● at AC at 50 Hz rated value minimum | 220 V |
● at AC at 50 Hz rated value maximum | 250 V |
● at AC at 60 Hz rated value minimum | 220 V |
● at AC at 60 Hz rated value maximum | 250 V |
pulse duration minimum | 50 ms |
Connections |
stripped length | 10 mm |
connectable conductor cross-section solid | |
● minimum | 0.75 mm² |
● maximum | 1.5 mm² |
connectable conductor cross-section stranded | |
● minimum | 0.75 mm² |
● maximum | 1.5 mm² |
connectable conductor cross-section finely stranded with core end
processing | |
● minimum | 0.75 mm² |
● maximum | 1.5 mm² |
tightening torque | |
● minimum | 0.6 N·m |
● maximum | 0.8 N·m |
Mechanical Design |
height | 230 mm |
width | 215 mm |
depth | 180 mm |
net weight | 7 865 g |
Environmental conditions |
ambient temperature during operation | |
● minimum | -25 °C |
● maximum | 70 °C |
ambient temperature during storage | |
● minimum | -40 °C |
● maximum | 80 °C |
Certificates |
reference code according to IEC 81346-2 | M |