China Bently Nevada Vibration Monitoring System manufacturer
SC Automation Limited
3
Home > Products > MTL Safety Barrier >

HART MTL4541 MTL Safety Barrier Repeater Power Supply

HART MTL4541 MTL Safety Barrier Repeater Power Supply

Brand Name MTL
Model Number MTL4541
Certification CE
Place of Origin USA
Minimum Order Quantity 1 piece
Price negotiable
Payment Terms T/T
Supply Ability 100pcs per month
Delivery Time on request
Packaging Details standard carton packing
Number of channels one
Location of transmitte Zone 0, IIC, T4–6 hazardous area if suitably certified Div. 1, Group A hazardous location
Safe-area circuit ripple < 50µA peak-to-peak
Temperature drift < 0.8µA/°C
Communications supported HART (terminals 1 & 2 only)
LED indicator Green: power indication
Detailed Product Description

MTL4541 REPEATER POWER SUPPLY

The MTLx541 provides a fully-floating dc supply for energising a conventional 2- or 3-wire 4/20mA transmitter, which is located in a hazardous area, and repeats the current in another floating circuit to drive a safe-area load. For HART 2-wire transmitters, the unit allows bi-directional communications signals superimposed on the 4/20mA loop current. Alternatively, the MTLx541S acts as a current sink for a safe-area connection rather than driving a current into the load. Separately powered current sources, such as 4-wire transmitters, can be connected but will not support HART communication.

 

SPECIFICATION

Number of channels

One

Location of transmitter

Zone 0, IIC, T4–6 hazardous area if suitably certified

Div. 1, Group A hazardous location

Safe-area output

Signal range: 4 to 20mA

Under/over-range: 0 to 24mA

Safe-area load resistance (MTLx541)

@ 24mA: 0 to 360Ω

@ 20mA: 0 to 450Ω

Safe-area load (MTLx541S)

Current sink: 600Ω max.

Maximum voltage source: 24V dc

Safe-area circuit output resistance: > 1MΩ

Safe-area circuit ripple

< 50µA peak-to-peak

Hazardous-area input

Signal range: 0 to 24mA (including over-range)

Transmitter voltage: 16.5V at 20mA

Transfer accuracy at 20°C

Better than 15µA

Temperature drift

< 0.8µA/°C

Response time

Settles to within 10% of final value within 50µs

Communications supported

HART (terminals 1 & 2 only)

LED indicator

Green: power indication

Maximum current consumption (with 20mA signal)

51mA at 24V

Power dissipation within unit (with 20mA signal)

MTLx541 0.7W @ 24V dc

MTLx541S 1.0W @ 24V dc

Safety description

Terminals 2 to 1 and 3:

Uo =28V Io =93mA Po =651mW Um = 253V rms or dc Terminals 1 to 3:

Simple apparatus ≤1.5V, ≤0.1A and ≤25mW; can be connected without further certification into any IS loop with an open-circuit voltage <28V

 

Related Part Number:

 

HCU16MTL5521MTL4546YMTL7761PAC
HCU3700MTL5522MTL4549YMTL7765AC
HM64RIB20-1.0MTL5531MTL4573MTL7787+
HM64RIB20-1.5MTL5532MTL4575MTL7787P+
HMM64MTL5541MTL4646YMTLCPS16
HMRIB16-1.0MTL5541SMTL4850NJ5-18GK-N
HMS64MTL5544MTL4851SD150X
HTP-SC32MTL5544DMTL4852SD32
MTL4044DMTL5546MTL5018SD32X
MTL4511MTL5546YMTL5032SDRTD
MTL4516MTL5561MTL5042SLP32D
MTL4516CMTL5573MTL5044TP48-3-I-NDI
MTL4521MTL5575MTL5049TP48-3-N-NDI
MTL4541MTL5582BMTL5511TP48-4-I-NDI
PCL45USBMTL7728+MTL5514DTP48-4-N-NDI
MTL4544MTL7756ACMTL5516TP48-N-NDI
MTL4544DMTL7760ACMTL5516CZB24571

 

Product Tags: HART MTL Safety Barrier   MTL4541 MTL Safety Barrier   repeater power supply USA  