MTL5521 MTLx521 SOLENOID ALARM DRIVER CE
|
MTL5521 SOLENOID/ ALARM DRIVERThe MTLx521 and the MTL4521L are loop-powered modules which enable a device located in the hazardous area to be controlled from the safe area. They can all drive a certified intrinsically safe low-power load, as well as non-energy-storing simple apparatus such as an LED.
SPECIFICATION Number of channels:One Location of load:Zone 0, IIC, T4–6 hazardous area if suitably certified Div. 1, Group A hazardous location Input voltage:20 to 35V dc Hazardous-area output (MTLx521):Minimum output voltage: 13.6V at 48mA;Maximum output voltage: 24V from 180Ω;Current limit: 48mA minimum Hazardous-area output (MTL4521L):Minimum output voltage: 11.1V at 48mA;Maximum output voltage: 24V from 232Ω;Current limit: 48mA minimum Output ripple:< 0.5% of maximum output, peak to peak Response time:Output within 10% of final value within 100ms LED indicator:Yellow: output status, on when output active Maximum current consumption:90mA at 24V Power dissipation within unit:1.4W at 24V Safety description (MTLx521):Uo =25V Io =147mA Po =0.92W Um = 253V rms or dc Safety description (MTL4521L):Uo = 25V Io = 108mA Po = 0.68W Um = 253V rms or dc
Related Part Number:
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Product Tags: MTL5521 MTLx521 ALARM DRIVER ALARM DRIVER CE |
|
EATON MTL661 Loop Powered Indicator for Zone 2 Hazardous Areas with ± 0.01mA Accuracy and Aluminium Case |
|
MTL7798 DIN-rail mounting safety barrier |
|
SD32MXL-CCN ETN MTL SD Modular module insert |
|
ETN MTL5581 isolator safety barrier |
|
ETN MTL5576-THC temperature converter |
|
SLP32D Eaton Crouse-Hinds series MTL SLP surge protector |